HUMI-DP-XR-D | Amphenol Advanced Sensors | Humidity
Duct Humidity Transmitter, Dew Point and Dry Bulb, ±1.8°F, -20° to 120°F
Manufacturer:Amphenol Advanced Sensors
MPN:HUMI-DP-XR-D
SKU:DP4A-D
availability:Call Kele For Availability
add to cart

product specifications
Accessory
DCP-1.5-W||DCPA-1.2||691-K0A
Application
Dew Point||Energy Management Systems||Hospital||Lab||Refrigeration Control||Pharmacy||Economizer||Supermarkets||Condensation Prevention
Description
Duct Humidity Transmitter, Dew Point and Dry Bulb, ±1.8°F, -20° to 120°F
Dew Point Accuracy
±1.8°F||±1°C
Dew Point Range
-20° to 120°F||-28.8° to 49°C
Feature
Transmitter
Housing Material
Poly
Housing Rating
IP42
Output
4-20 mA||0-5 VDC||0-10 VDC
Short Description
HUMIDITY XMTR, DUCT, FLD SEL OUT, -20° TO 120°F
Type
Duct
product family features
- Dew point accuracy of ±1.8℉ (±1℃) over the specified range
- Enthalpy accuracy of ±2 BTU/lb over specified range
- Wet bulb accuracy of ±3℉ over the specified range
- Dry bulb accuracy of ±.05℉ (±0.9℃)over the specified range
- Two 4-20 mA output signals
- Microprocessor-based signal processing
- Weather resistant duct/OSA mounting
- Temperature compensated
more information & related documents
Family Description
The Amphenol Advanced Sensors Model DP4 Dew Point, WB4 Wet Bulb, and EN4 Enthalpy Transmitters are rugged and compact. Each transmitter uses a capacitive RH sensor and an RTD temperature sensor to compute the dew point, wet bulb, or enthalpy for building automation and process applications. Two linear outputs provide a 4-20mA signal for dew point, wet bulb, or enthalpy, and a 4-20 mA signal for dry bulb. These transmitters are proven performers in Building Automation Systems, BAS, and HVAC applications.