KIP2-16.00-2-1 | Kele | Flow
Fan Inlet Flow Probe 16.00 Double Inlet Standard Mount
Brand:Kele
MPN:KIP2-16.00-2-1
SKU:KIP2-16.00-2-1
List Price:
$2,097.00
Today's Price:
$1,090.44
product specifications
Accuracy
2%
Type
Probe
Length
11-20 in
Max Temperature
350 °F
Velocity Range
100-10,000 FPM
product series specifications
- Supply Voltage: Not required
- Signal Output: Differential air pressure ports (Total P. & Static P)
- Min/Max Air Velocity: 100 to 8,000 fpm
- Velocity Formula: Velocity (FPM) = 4005 x ( v ?P in ?WC )
- Accuracy: ±2% over 100FPM
- Damper: N/A
- Damper Torque: N/A
- Straighting Vanes: N/A
- Sensor Type: Fan Inlet PITOT array w/ 2 ports, Total P. & Static P.
- Adjustments (Z/S): N/A
- Normal Measurement Range: .0006 ?WC to 4.0?WC
- Size Limits: Inlets from 16? to 80?
- Pressure Drop: .001 ?WC to 0.5 ?WC from 400 to 10K FPM
- Max Operating Pressure: Not specified
- Damper Leakage: N/A
- Operating Temperature: 20° to 350? (-6.7° to 177?)
- Operating Humidity: 0 to 100% Non-condensing
- In-Duct Parts:
- Media Compatibility: Clean HVAC duct air
- Process Connection: 1/4? barbs for 1/4? OD poly or copper tubing
- Wiring: Pressure transmitter per MNFR
- Mounting: Drill & screw on fan inlet lip
- Construction: 6063-T5 Anodized aluminum
- Enclosure Rating: N/A
- Dimensions: Made per order
- Weight: 1 to 12 lb. per order size
- Approvals: Not specified
- Warranty: 1 year
- Display: N/A
product series features
- Multiple total and static pressure sensing port
- Averaging internal manifold
- Insensitive to flow angle variations of as much as ±20 degrees when faced in the normal direction of flow
- Standard construction is 6063-T5 anodized aluminum
- Standard elements can be operate up to 350 degrees F
- All elements can be operated in humidity ranges of 0 to 100%
- Good salt air and mild acid resistance
more information & related documents
Series Description
The Kele KIP2 Series is an averaging airflow measuring element assembly specifically designed for installation in the inlet cone of centrifugal fans or inlet bell of vane-axial fans. The design of these primary elements provides a means of accurate measurement of fan capacity along with ease of installation. Each assembly is complete with two airflow measuring elements and pivot mounting hardware. The basic design is a in.cylindrical tube within a cylindrical tube in. creating independent chambers which permit the simultaneous measurement of both total pressure and static pressure. Kele is the leading supplier of building automation products. When you need the right product, right now, count on Kele.