VTI-2-P | Kele | Transducers
V/I XDCR,PANEL ENCL,DUAL OUT
Brand:Kele
MPN:VTI-2-P
SKU:VTI-2-P
List Price:
$318.00
Today's Price:
$165.36
product specifications
Mount
Panel Mount
Output
Analog
Supply Voltage
22-27 VDC
Type
Electronic
Output Signal
0-20 mA, 4-20 mA, 0-10 V, 1-5 V, 2-10 V
Input
Analog
Input Signal
1-19V, 4-20 mA
product series specifications
- Supply Voltage:
- 22-27 VDC, half-wave
- Supply Current:
- :
- VTI-1 50 mA
- :
- VTI-2 100 mA
- Input:
- 1-19 VDC range (1V minimum span) or 4-40 mA range
- Input Signal:
- Loss threshold 0.7 VDC
- Input Impedance:
- :
- VTI-1 301 kΩ @ 1-19 VDC; 250Ω @ 4-40 mA with 4 mA minimum span; 500Ω @ 2-38 mA with 2 mA minimum span; 750Ω @ 1.3-25 mA with 1.33 mA minimum span
- :
- VTI-2 150 kΩ @ 1-19 VDC; 250Ω @ 4-40 mA with 4 mA minimum span; 500Ω @ 2-38 mA with 2 mA minimum span; 750Ω @ 1.3-25 mA with 1.33 mA minimum span
- Action:
- Direct or reverse acting
- Linearity:
- <1% of span
- Output:
- :
- VTI-1 Single
- :
- VTI-2 Dual
- Output Burden:
- 850Ω maximum @ 24 VDC; Rmaximum=(Vsupply - 7)/20 mA
- Output Current:
- 4-20 mA
- Output Voltage:
- Reference voltage 10 VDC @ 15 mA maximum (1-19 VDC input), 6 VDC @ 10 mA maximum (1-11 VDC input)
- Wiring Terminations:
- Screw terminals
- Operating Temperature:
- 32° to 158‚Ñâ (0° to 70‚ÑÉ)
- Operating Humidity:
- 5% to 95% RH (non-condensing)
- Dimensions:
- :
- VTI-1 1.8"H x 2.3"W x 0.8"D (4.5 x 5.7 x 2.2 cm)
- :
- VTI-2 4.0"H x 2.3"W x 1.8"D (10.2 x 5.7 x 4.5 cm)
- Weight:
- :
- VTI-1 0.13 lb (0.06 kg)
- :
- VTI-2 0.38 lb (0.17 kg)
- Approvals:
- RoHS
- Warranty:
- 1 year
product series features
- Converts voltage, current or potentiometer signal into 4-20 mA signal
- Direct or reverse acting
- Loss of input signal results in 0 mA output
- LED indication of valid input signal (VTI-1)
- One input dual output model
- Independently configurable outputs
more information & related documents
Series Description
The VTI Series voltage and current converter/rescaler will convert voltage signals in the range of 1-19 volts into a 4-20 mA non-isolated signal. The voltage to current converter can also convert current signals in the range of 1.33-76 mA into a 4-20 mA non-isolated signal. The resulting current source signal can be direct or reverse acting for a variety of building automation and HVAC applications. These voltage to current converters can be used to drive grounded 4-20 mA loads utilizing a single power supply. The VTI also accepts an input from a resistive potentiometer. The VTI-1 is a single-input, single-output device, and the VTI-2 accepts a single input and provides dual outputs.
Kele Description
V/I XDCR,PANEL ENCL,DUAL OUT
Manufacturer
Kele