product specifications

Supply Voltage

20-30 VAC

Type

Communicating

product series specifications

    Supply Voltage:
  • 20-30 VAC, 50/60 Hz
    Accuracy :
  • ±0.9°F (±0.5°C) @ 70°F (21°C)
    Auxiliary Inputs:
  • Two dry contact digital inputs
    :
  • Four Types Service/status reminders
    :
  • Filter alarm
    :
  • Central night setback clock
    :
  • Remote occupied override timer
    Control Output:
  • 1A relays 30 VAC, 3A surge maximum
    Auxillary Contact Output:
  • 1A relay 30 VAC, N.O./N.C. follows occupied schedule
    Mixed Air Output:
  • Proportional 0-10V DC, 2 kŒ© minimum (economizer model)
    Display:
  • Two-line backlit LCD
    Controls:
  • Five menu-driven push buttons ‚Äì up, down, menu, no, yes/scroll
    Thermostat Type:
  • Seven-day programmable models, non-programmable models
    Optimal Start:
  • Progressive recovery (enable/disable)
    Heat Pump High/Low:
  • OSA lockout (emer heating/comp. heating)
    Stages:
  • (Dependent upon model) 1H/1C, 2H/2C, (3H/2C heat pump) 2H/2C + proportional mixed-air economizer
    Memory (schedule):
  • Permanent EEPROM
    Clock (12 or 24 hour):
  • Six-hour power fail retention
    System Switching:
  • Off/Auto/Cool/Heat
    Fan Switching:
  • On-continuous
    :
  • Auto-on demand
    :
  • Smart-on/occupied, off/unoccupied
    Setpoint Range:
    :
  • Heating 40° to 90°F (4.5° to 32°C)
    :
  • Cooling 54° to 100°F (12° to 37.5°C)
    Setpoint High/Low Limits:
  • Individually adjustable, H/C
    Remote Sensor :
    :
  • Room Sensor Room Sensor input auto-detected 10K Type 2 thermistors
    :
  • Outside Air Outside air input auto-detected 10K Type 2 thermistors
    :
  • Mixed Air Mixed air input auto-detected (economizer model only) 10K Type 2 thermistors
    Control Type:
  • Proportional plus integral
    Deadband:
  • Adjustable 2° to 4°F (1° to 2°C)
    OSA Lockout Limits:
    :
  • Heating 15° to 120°F (26° to 49°C), 5°F increments
    :
  • Cooling -40° to 95°F (-40° to 35°C), 5°F increments
    Low Limit Protection:
  • Enable/disable, heating @ 47°F (5.5°C)
    Power Up Delay:
  • 10 to 120 seconds
    Keypad Lockout:
  • Three levels (full, none, partial)
    Cycles Per Hour:
  • Adjustable, heating 3-8 CPH, cooling 3-4 CPH
    Display Offset:
  • Adjustable ±5°F (2.5°C), 1°F increments
    LED Indicators:
  • Three green on (fan, cooling, heating)
    Wiring:
  • 18 AWG max, 22 AWG recommended
    Operating Temperature:
  • 32° to 122°F (0° to 50°C)
    Operating Humidity:
  • 0% to 95% RH (non-condensing)
    Color :
  • White
    Mounting:
  • Standard vertical 2" x 4" box
    Enclosure Rating:
  • ULFR1 flame-retardant plastic
    Dimensions:
  • 4.94"H x 3.38"W x 1.13"D
    :
  • (12.5 x 8.6 x 2.9 cm)
    Weight:
  • 0.75 lb (0.34 kg)
    Approvals:
  • UL, cUL, File #E234137, CE
    Warranty:
  • 1 year

product series features

  • ALL MODELS
  • 1H/1C, 2H/2C (3H/2C heat pump) models
  • Fan switching (on/auto/smart)
  • System switching (O/A/C/H)
  • Two line 8 digit backlit LCD Display
  • Three status LEDs (Fan, Clg, Htg)
  • Five control keys
  • Remote sensor and OSA sensor inputs
  • Adjustable deadband
  • PIR cover available
  • Permanent program retention
  • Two configurable DI inputs
  • Two line LCD display (F or C)
  • Proportional + Integral control
  • ECONOMIZER MODELS
  • Mixed-air (0-10V) control outputs
  • Mixed-air sensor input
  • Mixed-air setpoint (SP)
  • Economizer changeover S.P. temperature
  • OSA damper minimum position in
  • PROGRAMMABLE MODELS
  • Two or four configurable events per day
  • Progressive recovery or none
  • 12 or 24 hour clock
  • Six hour clock retention
  • Occ/Unocc auxiliary contact out
  • COMMUNICATION MODELS
  • BACnet
  • LON
  • Wireless
  • Wireless/ Zigbee Pro

more information & related documents

Series Description

The Viconics VT7600 Communicating Thermostats are digital display, single or multistage, seven-day programmable or nonprogrammable PI thermostats (F or C) for use with AHU controls and heat pumps for both heating and cooling applications. The VT7600 has both system and fan switching with internal sensor or remote sensor capabilities. Five buttons control a simplified menu for over 20 configurable parameters. A communication card is added for multiple protocols, including BACnet and LON. Other control features are listed below.