Type
RTD
Housing Material
Poly
Sensor Element
100 Ohm Platinum RTD 385
Housing Style
Strap-On
Strap Pipe Diameter
1.25 to 4.00 in
Transmitter Temperature Range
0 to 100 °F (-17 to 38 °C)
Output
0 - 10 V
Lead Length
14 in
Enclosure Rating
NEMA 4X
Accessory
#20,APB-28,PN-46,TCC-111,TCC-12,T85U-XR,T81U-XR,T91U-XR,UR,DCP-1.5-W,DCPA-1.2
Feature
Transmitter
Application
Cold Water Systems,Hot Water Systems,Retrofit,Hydronic Heating Systems,Chillers
product series specifications
Accuracy: ±0.36°F (0.2°C)
Thermistor: ±0.36°F (0.2°C)
RTD: ±0.50°F (0.28°C)
Sensor Type:
Thermistor: 10 kΩ Type II & III, 20 kΩ, 100 kΩ
RTD: 100Ω, 1000Ω 385 curve
Temperature Range: -40° to 200°F (-40° to 150°C)
Stability:
Thermistor: 0.24°F (0.13°C) over five years
RTD:<±0.1°C drift
Heat Dissipation: Thermistor, 3 mW/°C (power needed to raise the temperature by 1°C)
Enclosure Rating: NEMA 1, Galvanized metal box
Wiring Terminations: 10" of 22 AWG wire or terminal strip
Weight: 0.8 lb (0.36 Kg)
Approvals: RoHS, CE
Warranty: 5 years
product series features
- Fits pipes 2 in to 5 in (5.1 to 12.7 cm)
- Two-year warranty
- Stainless steel strap
more information & related documents
Series Description
The ACI Strap On Series Thermistor and RTD Sensors are designed specifically for HVAC system temperature control. The strap-on sensors come in thermistor and RTD sensor curves compatible with most BAS systems available today. Strap-on sensors come with a handy box and stainless steel strap for 5 in (12.7 cm) pipes. The ACI Strap-On Sensor mounts directly to a 2 in to 5 in (5.1 to 12.7 cm) pipe. Clean off any insulation or rust to promote solid contact of the copper plate to the pipe. Wrap and tighten the strap around the pipe and compress the foam fully for a firm mount. Faster response can be achieved by using TCC-12 thermal conductive compound.
Kele Description
STRAP ON XMT 100 RTD 0-100F 2/10V WTHR PRF BOX
Manufacturer
ACI