DPA3-10

DPA3-10 | Kele | Pressure

Air Differential Pressure Transmitter, Multi-Range, ±0.5%, 0-10 WC, ±10 WC, 4-20 mA, 0-5 VDC, 0-10 VDC, No LCD

Brand:Kele

MPN:DPA3-10

SKU:DPA3-10

List Price:

$300.00

Today's Price:

$156.00



Availability: 1 In Stock
Available Inventory
These numbers are estimates based on our Memphis location and subject to change without notice based on customer demand.

Need more?
Just order your desired quantity and we'll ship the available inventory immediately while we source the remaining quantity to get you all the products you need as soon as possible.

We can also reserve the available inventory and ship once we acquire the remaining quantity from the supplier. Just choose "Ship Complete" at checkout.

product specifications

Accuracy

±0.50%

Approvals

CE, RoHS, REACH, WEEE

Direction

Uni-Directional, Bi-Directional

Housing Rating

Flame Retardant Polycarbonate, UL94-5VA

Measurement

Inches of Water Column

Media Compatibility

Liquid/Gas

Mount

Wall, Din Rail Mount

Output

Field Selectable

Range

±10 in WC

Supply Voltage

4-20 MA

Type

Field Selectable

product series specifications

    Supply Voltage :
  • 4-20 mA output; 16-36 VDC (250‚Ѷ load max.) / 22-36 VDC (500‚Ѷ load max.)
    :
  • 0-5 VDC / 0-10 VDC output; 16-36 VDC / 24 VAC (+/-10%)
    Supply Current :
  • 4-20 mA output; 24 mA minimum / 0-5 VDC / 0-10 VDC output; 6 mA max.)
    Output Signals:
  • Current output; 4-20 mA, 2-wire loop powered (standard); (Current limited to 21.4 mA max)
    :
  • Voltage signals; 0-5 VDC/ 0-10 VDC Field selectable, 3-wire; output limited @ 5.25 & 10.5 VDC)
    Response Time:
  • (0-100% FSO) 8 seconds
    Output Data Rate:
  • 1 second
    Pressure Ranges:
  • Multi range units (see ordering guide)
    Accuracy:
  • ± 0.5% FSO
    Zero Function:
  • Pushbutton Zero Function
    Thermal Effects:
  • +/-0.067% FSO /‚Ñâ (0.12% FSO/‚ÑÉ)
    Proof Pressure or:
    Burst Pressure:
  • DPA3-1, Proof: 270 inWC (67.2 kPa) / Burst: 415 inWC ) (103.3 kPa) for 1 inWC (249.8 Pa)
    :
  • DPA3-10, Proof: 350 inWC (87.12 kPa) / Burst: 550 inWC ) (139.9 kPa) for 10 inWC (2490.8 Pa)
    :
  • DPA3-40, Proof: 562 inWC (140 kPa) / Burst: 1004.7 inWC ) (250 kPa) for 40 inWC (9963.6 Pa)
    Operating Temperature:
  • -4 to 185‚Ñâ (-20 to 85‚ÑÉ)
    Compensated Temperature Range:
  • 32 to 122‚Ñâ (0 to 50‚ÑÉ)
    Storage Temperature:
  • -22 to 185‚Ñâ (-30 to 85‚ÑÉ)
    Operating Humidity:
  • 10 to 95% RH, non-condensing
    Media Types:
  • Dry air or inert non-conductive gases
    Enclosure Material:
  • Flame Retardant Polycarbonate; UL94-5VA
    Wiring Connections:
  • Finger pushbutton (spring) terminal blocks; accepts 16-24 AWG wires
    Conduit Knockouts:
  • Watertight cordgrip installed (1/2‚Ä= NPT conduit fittings accepted when Cordgrip removed)
    Pressure Fitting Material:
  • Nickel Plated Brass or Stainless Steel
    Tubing Size Accepted:
  • 1/4‚Ä= O.D. x 0.170‚Ä= I.D. Poly Tubing
    Dimensions:
  • 4.25‚Ä=L x 2.25‚Ä=W x 6.125‚Ä=H
    Weight:
    No Pitot Tube or Din Rail:
  • Non-LCD Display Version: 0.53 lbs (0.240 Kg) | LCD Display Version: 0.58 lbs (0.263 Kg)
    With Pitot Tube & Din Rail:
  • Non-LCD Display Version: 0.80 lbs (0.363 Kg) | LCD Display Version: 0.85 lbs (0.385 Kg)
    Approvals:
  • CE, RoHS, REACH, WEEE
    Warranty:
  • 5 years

product series features

  • ± 0.5% FSO (NIST available)
  • Field selectable output 0-5V, 0-10V, 4-20 mA
  • 0.1 to 40 in WC (model dependent)
  • 8 Files selectable ranges

more information & related documents

Series Description

The Kele DPA3 Series Differential Low Pressure is based on a piezoresistive, silicon sensing element which senses Differential Pressure and provides an analog output. The hinged cover on the DPA3 can be easily opened using the integrated locking tab on the side of the enclosure. This allows for easy access to the zero function and field selectable ranges and outputs. The DPA3 Series also includes an optional, five digit LCD for installation and monitoring support. The standard accuracy of this series is ±0.5% FSO. Field selectable analog outputs include 0-5 and 0-10 VDC, or 4-20mA which correlate to a uni or bidirectional pressure range from 0-0.1 in up to 0-40 in of water column, depending on your model selection. Each unit has up to 8 field selectable, uni or bidirectional ranges. Kele is the leading supplier of building automation products. When you need the right product, right now, count on Kele.

Kele Description

AIR DIFF PRESS XMTR, MULTI, +/-0.50%, 0-10" WC, +/-10" WC, FLD SEL OUT, NO LCD, DIN RAIL, WALL

Manufacturer

Kele

x