DL10-01

DL10-01 | Flowline | Level

Ultrasonic Level Transmitter, 49.2 inches W/Fob

Brand:Flowline

MPN:DL10-01

SKU:DL10-01

List Price:

$1,044.00

Today's Price:

$542.88



Availability: 3 In Stock
Available Inventory
These numbers are estimates based on our Memphis location and subject to change without notice based on customer demand.

Need more?
Just order your desired quantity and we'll ship the available inventory immediately while we source the remaining quantity to get you all the products you need as soon as possible.

We can also reserve the available inventory and ship once we acquire the remaining quantity from the supplier. Just choose "Ship Complete" at checkout.

product specifications

Range

30 psi

Supply Voltage

24 VDC

Type

Ultrasonic Level Transmitter

Display

No

Cable Length

48 in

Sensing Type

Ultrasonic

product series specifications

    Supply Voltage:
  • 24 VDC, 25 mA
    Accuracy:
  • ±0.125" (3 mm)
    Signal Output:
  • 4-20 mA @ 400‚Ѷ (loop powered)
    Measurement Range:
  • 2" to 49.2" (50.8 to 1.25m)
    Memory:
  • Non-volatile
    Deadband:
  • 2" (5.1 cm)
    Operating Pressure:
  • 30 psig (206.9 kPa)
    Process Temperature:
  • 20° to 140‚Ñâ (-7° to 60‚ÑÉ)
    Beam Width:
  • 2" (5.1 cm)
    Fail Safe:
  • Signal 4 mA, 20 mA, 21 mA 22 mA, or hold last signal
    Resolution:
  • 0.019" (0.5 mm)
    Temperature Compensation:
  • Automatic
    Process Connection:
  • 1" NPT
    Cable Length:
  • 48" (1.2 m)
    Operating Temperature:
  • -31° to 140‚Ñâ (-35° to 60‚ÑÉ)
    Enclosure Rating:
  • Polycarbonate, NEMA 6P
    Dimensions:
  • 3.2"H x 2.0"W x 2.0"D (8.1 x 5.1 x 5.1 cm)
    Weight:
  • 3.0 lbs (1.4 Kg)
    Approvals:
  • CE, FM, RoHS
    Warranty:
  • 1 year

product series features

  • Ideal for small tank applications
  • Simple configuration
  • Enclosure designed to be corrosion resistant
  • Minimal dead band to top of liquid optimizes filling capacity
  • Adjustable loop failsafe
  • 2 in (5.1 cm) beam diameter for restricted spaces
  • Transmitters can be quickly configured using WebCal software

more information & related documents

Series Description

The compact Model DL10 Ultrasonic Level Transmitter provides non-contact liquid level measurement up to 49.2 in (1.25m) with reversible 4-20 mA output. The Model DL10 is ideal for corrosive, sticky and dirty media. Engineered for use in Building Automation Systems, BAS, and HVAC applications, the transmitters can be quickly configured using WebCal software. The software offers pre-programmed menus, tank setpoint graphics, and custom wiring diagrams. The user can define loop failsafe, start-up condition, output at empty and specific tank levels.

Kele Description

ULTRASONIC LEVEL TRANSMITTER, 49.2IN W/FOB

Manufacturer

Flowline

x