GEH2-O-TT4B | Telaire/Amphenol | Humidity

Humidity Transmitter, OSA, ±2.00%, -20° to 140°F, Conduit Fitting

Brand:Telaire/Amphenol

MPN:GEH2-O-TT4B

SKU:GEH2-O-TT4B

List Price:

$549.00

Today's Price:

$285.48

Call 877.826.9045 for availability

CALL FOR AVAILABILITY

Call 877.826.9045 for more information about this part's availability.

product specifications

Accuracy

2%

Housing Material

Poly

Sensor Element

10K Thermistor

Temperature Range

-20 to 140 °F (-29 to 60 °C)

Output

4 - 20 mA

Enclosure Rating

IP42

Power Requirements

12-30 VDC

Accessory

DCPA-1.2,DCP-1.5-W,T81U-XR,T85U-XR,UR

Feature

Conduit Fitting

Application

Outdoor Air Humidity,Economizer Control,Psychrometric Calculations,Enthalpy,Dew Point,Wash Down Applications

Mount

OSA

product series specifications

Accuracy: 2% (10% to 90%)

Supply Voltage: 12-30 VDC, 100mA

Signal Output: 4-20 mA @ 700Ω, 0-5V/0-10V selectable @ 10KΩ max.; 0-100% RH

Sensing Technology: Capacitive and replaceable

Operating Humidity: 0% to 99%, non-condensing

Operating Temperature: -40° to 140°F (-40° to 60°C)

Enclosure Rating:

Room: ABS plastic, UL94V Room Installed IP20, NEMA 1

Duct/OSA: IP42, NEMA 3R Stainless steel with removable tip, PTFE Teflon® shield

Wiring Terminations: 16 to 22 AWG terminals

Weight:

Room: 0.34 lb (0.15 Kg)

Duct: 0.96 lb (0.44 Kg)

OSA: 1.22 lb (0.55 Kg)

Warranty: 2 years

product series features

  • ±2% accuracy
  • Temperature compensated
  • Field-selectable 4-20 mA, 0-10V, or 0-5V outputs
  • Replaceable sensor
  • Optional temperature transmitter

more information & related documents

Series Description

The Amphenol Advanced Sensors Model GEH2 Series 2% Accuracy Humidity Transmitters are designed specifically for humidity measurement for commercial building automation systems, BAS, and HVAC applications. The room, duct and OSA transmitters use replaceable humidity sensor tips and switch selectable transmission including 4-20mA, 0-5 volt or 0-10 volt DC. The GEH also has an optional temperature transmitter output with selectable outputs (RH&T must be the same type). All duct and OSA enclosures are rated for IP42 or NEMA 3R applications.

Kele Description

2% OSA RH XMTR W/TEMP -20/140F W/CONDUIT HUB

Manufacturer

Telaire/Amphenol