TGM-A4X-A | Senva | Gas & Specialty Sensors
TGUL, METAL, ANALOG, R410A
Manufacturer:Senva
MPN:TGM-A4X-A
SKU:TGM-A4X-A
List Price:
$1,115.02
Today's Price:
$579.81
product family specifications
- Power Supply:
-  15-30VDC/24VAC(1), 4W max, 160mA max.
- Analog Outputs:
 2 programmable outputs: 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable) 
 CO output scaling: 0-200ppm (default), 0-1000ppm (menu selectable) 
 NO2 output scaling: 0-10ppm (default), 0-30ppm (menu selectable) 
 Temperature output scaling: -20 to 85oC 
- BACnet /Modbus:
 Protocol RS-485: BACnet MS/TP, Modbus RTU, Modbus ASCII 
 Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200 
 
- Fan Relay:
 Fan relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection) 
 CO fan relay setpoint: 25ppm (default), 0-1000 ppm (menu selectable) 
 NO2 fan relay setpoint: 1ppm (default), 0-30ppm (menu selectable) 
 
- Alarm Relay (Analog model only)  :
 Alarm relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection) 
 CO alarm relay setpoint: 100ppm (default), 0-1000 ppm (menu selectable) 
 NO2 alarm relay setpoint: 3ppm (default), 0-30ppm (menu selectable) 
- Display:
-  3-1/2 digit LCD: Indicates CO ppm, NO2 ppm (menu selectable)
- LEDs:
 Green, Yellow, Red: Green = Normal, Yellow = Relay, Red = Alarm 
 
- Audible Alarm Exposure :
-  85dB Piezo transducer: 30 minutes above alarm setpoint per UL2034 (menu selectable)
- CO Sensor Performance:
 Type: Electrochemical 
 Accuracy: ±5% of default range(2) ±5%of reading above menu selectable)
 Resolution: 1ppm 
 Certications: UL2034 Listed Component 
 Life expectancy: >7 years 
 Coverage Area: 5000-7500 square feet 
 
- NOSensor Performance:
 Type: Electrochemical 
 Accuracy: ±5% of default range(3) ±5% of default range(3) ±5%of reading above 20ppm 
 Resolution: 0.1ppm 
 Life expectancy: >7 years 
Coverage Area: 5000-7500 square feet 
- Methane Sensor Performance:
 Type: Catalytic 
 Detection Range: 0-50% LEL (Lower Explosive Limit) 
 Accuracy: 5% of range 
 Resolution: 1%LEL 
 Life expectancy: >5 years 
 Coverage Area: 5000 square feet 
 
- Propane Sensor Performance:
 Type: Catalytic 
 Detection Range: 0-50% LEL (Lower Explosive Limit) 
 Accuracy: 5% of range 
 Resolution: 1%LEL 
 Life expectancy: >5 years 
 Coverage Area: 5000-7500 square feet 
 
- Operating Environment:
 Temperature, continuous: -20 to 50oC 
 Humidity: 15-95% continuous, 0-95% intermittent 
 Max Elevation: 2000m 
 
- Enclosure (Wall & Duct):
 Material: ABS/Polycarbonate 
 Dimensions: 4.0”h x 4.4”w x 2.1”d 
 Conduit Opening: Tapped 1/2” NPT 
 Rating: IP20 
- Enclosure (Metal):
 Material & Enclosure Rating: Powder-coated steel/acrylic, NEMA 3R 
 Dimensions: 5.0”h x 4.3”w x 2.25”d 
 Opening: Dual air vents on the bottom of the enclosure 
 Mounting: Pre-drilled for 2x4” electrical box 
 Rating: IP20 
- Approvals:
-  Compliance UL61010-1 Listed UL, cUL
-   7 years
product family features
more information & related documents
Family Description
Senva TG UL Series wall and duct sensors can be ordered as individual sensors or as any dual combination of CO / NO2 / CO2 / Methane / Propane / Hydrogen / Oxygen / H2S / Ammonia / Refrigerants sensor in a shared enclosure. The analog output model features two outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost-effective coverage of large areas. The unit can also act as a stand-alone controller, utilizing the relay for exhaust fan operation, or the output for direct control of a VFD. The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display, and audible alarm.
Kele Description
TGUL, METAL, ANALOG, R410A
Manufacturer
Senva