GDN-BCO-1 | Kele | Gas & Specialty Sensors
Co Network Carbon Monoxide Gas Detector Bacnet
Brand:Kele
MPN:GDN-BCO-1
SKU:GDN-BCO-1
List Price:
$1,607.76
Today's Price:
$836.04
product specifications
Application
Industrial, Oil & Gas, Labs, Agriculture, Transportation, Mining
Measurement Range
0-250 ppm
Output
BACNET
Display
Yes
Output Type
Communicating
Mounting Location
Wall
product series specifications
- Supply Voltage:
- 17-27 VAC @ 8.4 VA, 50/60 Hz or 24-38 VDC @ 350 mA
- Accuracy:
- ±3%
- Communication:
- RS485 Modbus, Bacnet MS/TP
- Measurement Range:
- CO:
- 0-250 ppm
- O2:
- 0% to 25%
- H2S:
- 0-50 ppm
- N2O:
- 0-10 ppm
- CH4, C3H8, H2:
- 0% to 100% LEL
- Sensing Technology:
- CO, O2, H2S,NO2:
- Electrochemical
- CH4, C3H8, H2:
- Catalytic combustion
- Calibration Interval:
- 6 months
- Life Expectancy:
- CO:
- 6 years
- Alll Others:
- 2 years
- Visual Indication:
- Green LED: power
- Amber LED 1: Alarm/fault :
- Amber LED 2: Alarm/fault:
- Response Time:
- 50 seconds or less
- Display:
- 8 character, two-line LCD
- Relay Output:
- (1) DPDT pilot duty, 150 VA max inductive, 5A @ 30 VDC, 250 VAC
- Alarm Auditory Levels Db:
- 85 dBA @ 10 ft (3m)
- Display Resolution:
- 0.5%, 1 ppm, 0.2 ppm, 0.2%, 0.5%.
- Operating Temperature:
- CO:
- -4° to 122°F (-20° to 50°C)
- All Others:
- -40° to 122°F (-40° to 50°C)
- Operating Humidity:
- 15 to 90% non-condensing
- Dimensions:
- 8.1''H x 5.9''W x 2.7''D (20.6 x 14.9 x 6.7 cm)
- Weight:
- 1.84 lb (0.83 Kg)
- Approvals:
- ETL
- Warranty:
- 1 year
product series features
- Modbus or BacNet MS/TP compatible
- Pre-calibrated plug-in sensors
- Built-in 85 dBA buzzer
- Wide variety of gases detected
- Two-line LCD display
- DPDT relay output
- Easy installation, commissioning, and operation
- LED status indication
- Password protection
- Programmable relay differential
more information & related documents
Series Description
The Kele GDN Series Network Compatible Gas Detector optimizes BAS, fire, ventilation, and other security systems by providing continuous monitoring of toxic and combustible gases. Modbus or BACnet MS/TP protocols are supported by the GDN Series and can be quickly integrated into a BAS network. Activate alarms, horns, strobes, and fans through HVAC controls or directly from the on-board relay. The modular design adds functionality and flexibility with pre-calibrated plug-in sensors. The unit features a two-line LCD for local indication, self test diagnostics, and a built-in 85 dBA buzzer. The GDN Series is designed to be used as part of a control system that helps to prevent the formation of a hazardous environment when properly installed and maintained.
Kele Description
CO NETWORK CARBON MONOXIDE GAS DETECTOR BACNET
Manufacturer
Kele