TGW-AOX-A
* product series image displayed

TGW-AOX-A | Senva | Gas & Specialty Sensors

TGUL, WALL, ANALOG, OXYGEN

Brand:Senva

MPN:TGW-AOX-A

SKU:TGW-AOX-A

List Price:

$1,064.00

Today's Price:

$553.28



Availability: Lead time > 15 days. See alternatives below or chat with Sales.
Available Inventory
Lead times are estimates based on our Memphis location and subject to change without notice based on customer demand.

Need more?
Just order your desired quantity and we'll ship the available inventory immediately while we source the remaining quantity to get you all the products you need as soon as possible.

We can also reserve the available inventory and ship once we acquire the remaining quantity from the supplier. Just choose "Ship Complete" at checkout.

product specifications

Application

Industrial, Oil & Gas, Labs, Agriculture, Transportation, Mining

Measurement Range

0 - 25%

Output

0 - 5/10 V|1 - 5 V |4 - 20 mA

Display

Yes

product series specifications

    Power Supply:
  • †15-30VDC/24VAC(1), 4W max, 160mA max.
    Analog Outputs:
  • †2 programmable outputs: 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable)

    †CO output scaling: 0-200ppm (default), 0-1000ppm (menu selectable)

    †NO2 output scaling: 0-10ppm (default), 0-30ppm (menu selectable)

    †Temperature output scaling: -20 to 85oC

    BACnet /Modbus:
  • †Protocol RS-485: BACnet MS/TP, Modbus RTU, Modbus ASCII

    †Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200

    Fan Relay:
  • †Fan relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)

    †CO fan relay setpoint: 25ppm (default), 0-1000 ppm (menu selectable)

    †NO2 fan relay setpoint: 1ppm (default), 0-30ppm (menu selectable)

    Alarm Relay†(Analog model only)†:
  • †Alarm relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)

    †CO alarm relay setpoint: 100ppm (default), 0-1000 ppm (menu selectable)

    †NO2 alarm relay setpoint: 3ppm (default), 0-30ppm (menu selectable)

    Display:
  • †3-1/2 digit LCD: Indicates CO ppm, NO2 ppm (menu selectable)
    LEDs:
  • †Green, Yellow, Red: Green = Normal, Yellow = Relay, Red = Alarm


    Audible Alarm†Exposure†:
  • †85dB Piezo transducer: 30 minutes above alarm setpoint per UL2034†(menu selectable)
    CO Sensor Performance:
  • †Type: Electrochemical

    †Accuracy: ±5% of default range(2) ±5%of reading above†menu selectable)

    †Resolution: 1ppm

    †Certications: UL2034 Listed Component

    †Life expectancy: >7 years

    †Coverage Area: 5000-7500 square feet

    NOSensor†Performance:
  • Type: Electrochemical

    †Accuracy: ±5% of default range(3) ±5% of default range(3) ±5%of reading above 20ppm

    †Resolution: 0.1ppm

    †Life expectancy: >7 years

    Coverage Area: 5000-7500 square feet

    Methane Sensor†Performance:
  • †Type: Catalytic

    †Detection Range: 0-50% LEL (Lower Explosive Limit)

    †Accuracy: 5% of range

    †Resolution: 1%LEL

    †Life expectancy: >5 years

    †Coverage Area: 5000 square feet

    Propane Sensor†Performance:
  • †Type: Catalytic

    †Detection Range: 0-50% LEL (Lower Explosive Limit)

    †Accuracy: 5% of range

    †Resolution: 1%LEL

    †Life expectancy: >5 years

    †Coverage Area: 5000-7500 square feet

    Operating Environment:
  • †Temperature, continuous: -20 to 50oC

    †Humidity: 15-95% continuous, 0-95% intermittent

    †Max Elevation: 2000m

    Enclosure†(Wall & Duct):
  • †Material: ABS/Polycarbonate

    †Dimensions: 4.0‚Äùh x 4.4‚Äùw x 2.1‚Äùd

    †Conduit Opening: Tapped 1/2‚Äù NPT

    †Rating: IP20

    Enclosure†(Metal):
  • †Material & Enclosure Rating: Powder-coated steel/acrylic, NEMA 3R

    †Dimensions: 5.0‚Äùh x 4.3‚Äùw x 2.25‚Äùd

    †Opening: Dual air vents on the bottom of the enclosure

    †Mounting: Pre-drilled for 2x4‚Äù electrical box

    †Rating: IP20

    Approvals:
  • †Compliance UL61010-1 Listed UL, cUL
    Warranty
    :
  • † 7 years

product series features

  • Cost-effective dual gas sensing and control
  • Flexibility of analog output model
  • Versatility with BACnet/Modbus model. High reliability reduces callbacks
  • Easy to install

more information & related documents

Series Description

Senva TG UL Series wall and duct sensors can be ordered as individual sensors or as any dual combination of CO / NO2 / CO2 / Methane / Propane / Hydrogen / Oxygen / H2S / Ammonia / Refrigerants sensor in a shared enclosure.   The analog output model features two outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost-effective coverage of large areas. The unit can also act as a stand-alone controller, utilizing the relay for exhaust fan operation, or the output for direct control of a VFD. The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display, and audible alarm.

Kele Description