69313-004 | Badger Meter | Flow

MODBUS TCP COMMUNICATION OPTION CARD (FITS INTO THE ONE CENTER CARD SLOT)

Brand:Badger Meter

MPN:69313-004

SKU:69313-004

List Price:

$1,775.00

Today's Price:

$923.00

Lead time of 15 days. Chat with Kele experts now

product specifications

Type

Accessory

product series specifications

System: Most clean liquids or liquids containing small amounts of suspended solids or gas bubbles

Flow Accuracy:

Medium and Large Pipes (RZ, NZ, WZ, HZ, LZ, YZ, JZ, KZ): ± 0.5% ± 0 0.049 ft/s (0.015 m/s)


Small Pipes (CA-CT, UZ): 1 in. (25 mm) and larger = ±1% ± 0.03 ft/s (0.009 m/s) 3/4 in. (20 mm) and smaller = ±1% of full scale

Repeatability: 0.2% above 1.5 ft/s

Velocity Medium and Large Pipes:Up to 40 ft/s, depending on pipe and fluid

Small Pipes: Up to 20 ft/s, depending on pipe and fluid

Straight Run Requirements: 10 diameters upstream, 5 diameters downstream from single elbow

See Datasheet for more information*

product series features

  • Large, bi-directional flow measuring range
  • Data log up to 8 records
  • Modbus® RTU or BACnet® MS/TP over EIA-485; Modbus TCP/IP; BACnet/IP; AquaCUE®/BEACON® connectivity
  • Configure and troubleshoot over USB with SoloCUE
  • Reynolds, ultrasonic speed and temperature compensation
  • Large, easy-to-read graphical display
  • Rugged, aluminum enclosure for a long service life in harsh environments

more information & related documents

Series Description

The TFX-5000 transit time ultrasonic flow meter measures volumetric flow and heating/cooling energy rates in clean liquids as well as those with small amounts of suspended solids or aeration, such as surface water or raw sewage.TFX-5000 flow and energy meters clamp onto the outside of pipes and do not contact the internal liquid.

Kele Description

MODBUS TCP COMMUNICATION OPTION CARD (FITS INTO THE ONE CENTER CARD SLOT)

Manufacturer

Badger Meter