23-197 | Fireye | Combustion Control & Flame Safety
REPLACEMENT FUSE FOR MICROM MEC120
Brand:Fireye
MPN:23-197
SKU:23-197
List Price:
$4.00
Today's Price:
$2.08
Log in for customized pricingproduct series specifications
Maximum Number of Burners: 20
Valve Operation: Simultaneous (all burners operate from a single fuel train)
Supply Voltage: 120VAC (+10%, -15%), 50/60 Hz
Power Consumption: 25VA
Flame Failure Response: 3 seconds (+/- 0.5 seconds)
Pilot Trial for Ignition: 5, 10, or 15 seconds (selectable)
Main Trial for Ignition: Follows Pilot Trial for Ignition selection
Purge Time: 0 seconds to 60 minutes (increment selectable depending on range)
Contact Ratings:
Fan Motor: 15 Amps Resistive (1/2 HP Inductive)
All Others: 10 Amps Resistive (1/3 HP Inductive)
Shipping Weight: 15 lbs (7 kilograms)
product series features
- 3 second flame failure response time (±0.5 seconds)
- 5-, 10-, or 15-second selectable pilot trial for ignition with 5-second pilot proving time
- Compatible with UV7 ultravoilet flame scanners
- Selectable purge time increments from 0-225 seconds in 15-second increments up to 0-60 minutes in 4-minute increments
- UL recognized, FM approved
more information & related documents
Series Description
Fireye's MB multi-burner monitoring system controls the start-up sequence and monitors the flame of up to 20 individual gas, oil or combination gas/oil burners connected to a common valve train. Dynamic on-board diagnostics check for faulty relays, proof of valve closure, high and low fire switch interlocks, and shortened air switch. It can specifically identify which burner caused the initial flame failure. The MB-600S chassis directly powers pilot and main gas valves and ignition transformers. The built in blower output, purge timing and modulation control, let you add independent limits and a controller to create a complete combustion control system for furnace, oven or other multi-burner applications.
Kele Description
REPLACEMENT FUSE FOR MICROM MEC120
Manufacturer
Fireye