45UV5-1009

45UV5-1009 | Fireye | Combustion Control & Flame Safety

Ultraviolet Self-Check Scanner, 1 NPT. Shutter Cycle Period: 0.4 Second Closed, 3.6 Second Open. 102-264 VAC Shutter Voltage. Temperature range: 40° to 200° F. Use with 72DUVS4, 72DUVS1T, BurnerLogix, E-Series, MicroM, FlameWorx II.

Brand:Fireye

MPN:45UV5-1009

SKU:45UV5-1009

List Price:

$4,834.62

Today's Price:

$2,514.00



Availability: Usually Ships in Less Than 5 Business Days
Available Inventory
Lead times are estimates based on our Memphis location and subject to change without notice based on customer demand.

Need more?
Just order your desired quantity and we'll ship the available inventory immediately while we source the remaining quantity to get you all the products you need as soon as possible.

We can also reserve the available inventory and ship once we acquire the remaining quantity from the supplier. Just choose "Ship Complete" at checkout.

product specifications

Type

Flame Scanner

Used With

Fireye 45UV5 Self-Checking Discrete Ultraviolet Flame Scanner

product series specifications

Housing Material: Cast aluminum

Weight: 7 lbs. (3.2 kg)

Purge Air: 4 SCFM (113L/min) at 3/8 inch threaded housing inlet or 4 SCFM at 1 inch wye fittingin scanner sight pipe. Temperatures near the upper limit of the scanner operating range and/or usewith dirty duels may require up to 15 SCFM (425 L/min.).

Optical Range: 2200 to 2600 angstroms. No response to infrared radiation or visible light.

Optical Field of View: 1 inch per foot (25.4mm/305mm)

Operating Range: 72 inches (1830mm) or less

Threads: Either 1" NPT or 1" BSP threads, depending on the model

Temperature Range: 45UV5-1005, 1105: -40° to 200°F (-40° to 93°C); 45UV5-1006, 1007, 1009: -40° to 200°F (-40° to 93°C)


product series features

  • The components are contained in a cast aluminum housing sealed with an oil-resistant gasket.
  • The quartz lens is a planoconvex design, resulting in increased sensitivity.
  • Scanner contains an electromagnetic shutter that permits a self-checking circuit to verify that the scanner and signal circuits are producing valid flame presence or absence information.
  • Compatible with Flame-Monitor, BurnerLogix, D-Series, FlameWorx, MicroM, and some P-Series Fireye control models.

more information & related documents

Series Description

Self-checking ultraviolet scanning capabilities make the Fireye 45UV5 ideal for continuously fired applications where recycling is infrequent or absent. These scanners can be used to detect ultraviolet emissions from fossil fuel flames such as natural gas, coke oven gas, propane, methane, butane, kerosene, light petroleum distillates, and diesel fuels. Self-checking circuit tests the electronics and the UV tube for proper operation every four seconds during the firing period. The Fireye 45UV5 also features a replaceable UV tube and shutter mechanism.

Kele Description

UV SELF-CHECK SCANNER, 1" NPT, 102-264 VAC SHUTTER. FOR BURNERLOGIX, E-SERIES, MICROM, FLAMEWORX II.

Manufacturer

Fireye