Gas and Specialty Sensors

IAQ-N Series



Product Bar End
Product Bar End

IAQ-N Series

Honeywell Analytics Network Compatible Indoor Air Quality Monitor IAQ-N Series

Honeywell Analytics Network Compatible Indoor Air Quality Monitor

 

The Honeywell Analytics IAQ-N Series provides indoor air quality monitoring of CO2, temperature, and RH for demand control ventilation applications. The monitor can be programmed for BACnet or Modbus communication for easy installation and integration into existing building automation systems. The IAQ-N Series features a two-line LCD display and programmable setpoints for CO2, humidity, and temperature. The unit is available for wall or duct mount installations and easily mounts to a standard electrical box.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
IAQ-DLC-D CO2 IAQPOINT LON DUCT ANALOG DISPLAY INFO1,012.00809.60
IAQ-DLC-R-D CO2 IAQPOINT LON DUCT ANALOG RELAY/DISP INFO1,034.00827.20
IAQ-DLC-TRH-R-D CO2 IAQPOINT LON DUCT ANALOG TEMP/RH/RELAY/DISP INFO1,145.00916.00
IAQ-DLV-D VOC IAQPOINT LON DUCT ANALOG DISPLAY INFO1,123.00898.40
IAQ-DLV-R-D VOC IAQPOINT LON DUCT ANALOG RELAY DISPLAY INFO1,145.00916.00
IAQ-DLV-TRH-D VOC IAQPOINT LON DUCT ANALOG TEMP/RH/DISP INFO1,234.00987.20
IAQ-DLV-TRH-R-D VOC IAQPOINT LON DUCT ANALOG TEMP/RH/RELY/DISP INFO1,256.001,004.80
IAQ-DNC-D CO2 IAQPOINT MONITOR DUCT NETWORK DISPLAY INFO900.00720.00
IAQ-DNC-R-D CO2 IAQPOINT MONITOR DUCT NETWORK RELAY/DISPLAY INFO923.00738.40
IAQ-DNC-TRH-R-D CO2 IAQPOINT MON DUCT NETWORK TEMP/RH/RELY/DISP INFO1,034.00827.20
IAQ-DNV-D VOC IAQPOINT MONITOR DUCT NETWORK DISPLAY INFO1,012.00809.60
IAQ-DNV-R-D VOC IAQPOINT MONITOR DUCT NETWORK RELAY/DISPLAY INFO1,034.00827.20
IAQ-DNV-TRH-D VOC IAQPOINT MONITOR DUCT NETWORK TEMP/RH/DISP INFO1,123.00898.40
IAQ-DNV-TRH-R-D VOC IAQPOINT MON DUCT NETWORK TEMP/RH/RELY/DISP INFO1,145.00916.00
IAQ-WLC-D CO2 IAQPOINT LON WALL NETWORK DISPLAY INFO867.00693.60
IAQ-WLC-R-D CO2 IAQPOINT LON WALL NETWORK RELAY/DISPLAY INFO889.00711.20
IAQ-WLC-TRH-D CO2 IAQPOINT LON WALL NETWORK TEMP/RH/DISP INFO978.00782.40
IAQ-WLC-TRH-R-D CO2 IAQPOINT LON WALL NETWORK TEMP/RH/RELY/DISP INFO1,000.00800.00
IAQ-WLV-D VOC IAQPOINT LON WALL NETWORK DISPLAY INFO978.00782.40
IAQ-WLV-R-D VOC IAQPOINT LON WALL NETWORK RELAY/DISPLAY INFO1,000.00800.00
IAQ-WLV-TRH-D VOC IAQPOINT LON WALL NETWORK TEMP/RH/DISP INFO1,089.00871.20
IAQ-WLV-TRH-R-D VOC IAQPOINT LON WALL NETWORK TEMP/RH/RELY/DISP INFO1,112.00889.60
IAQ-WNC-D CO2 IAQPOINT MONITOR WALL NETWORK DISPLAY INFO756.00604.80
IAQ-WNC-R-D CO2 IAQPOINT MONITOR WALL NETWORK RELAY/DISPLAY INFO778.00622.40
IAQ-WNC-TRH-D CO2 IAQPOINT MONITOR WALL NETWORK TEMP/RH/DISP In Stock867.00693.60
IAQ-WNC-TRH-R-D CO2 IAQPOINT MON WALL NETWORK TEMP/RH/RELY/DISP INFO889.00711.20
IAQ-WNV-D VOC IAQPOINT MONITOR WALL NETWORK DISPLAY INFO867.00693.60
IAQ-WNV-R-D VOC IAQPOINT MONITOR WALL NETWORK RELAY/DISPLAY INFO889.00711.20
IAQ-WNV-TRH-D VOC IAQPOINT MONITOR WALL NETWORK TEMP/RH/DISP INFO978.00782.40
IAQ-WNV-TRH-R-D VOC IAQPOINT MON WALL NETWORK TEMP/RH/RELY/DISP INFO1,000.00800.00

Accessories

No accessories found
Features
  • Senses CO2, temperature, and RH
  • High accuracy
  • BACnet or Modbus communication
  • Menu driven operation
  • User selectable gas detection range
  • Easy calibration
  • Backlit LCD
  • Independent sensor operation
  • ABC logic
Specifications

Supply Voltage:20-30 VAC @ 6.7 VA, 50/60 HZ or 18-30 VDC @ 281 mA

Accuracy:CO2: ± 3%, 0-2000 ppm;

RH: 0% to 95% noncondensing:

Temperature: ± 0.9°F @ 77°F (0.5°C @ 25°C):

Measurement Range:CO2: 0-2000 ppm, 0-5,000 ppm (jumper selectable)

Humidity: 0% to 95% noncondensing:

Temperature: 32° to 122°F (0° to 50°C):

Relay Type:SPDT, 3 A @ 250 VAC or 30 VDC, field configurable

Sensing Technology:

 :CO2: Non-dispersive infrared (NDIR)

RH and temperature: Capacitive:

Display:Graphic LCD; two-line, alphanumeric

Response Time:CO2: <60 seconds for 90% step change Humidity: 4 seconds Temperature: 30 seconds

Baud Rate:4800, 9600, 19200, 38400, 57600, 76800, 115200

Communication Protocol:BACnet, MS/TP, Modbus

Minimum Duct Velocity:420 ft/min (2 m/s)

Operating Temperature:32° to 122°F (0° to 50°C)

Operating Humidity:0% to 95% RH

Dimensions:

Wall:4.6"H x 3.0"W x 1.5"D (11.8 x 7.7 x 3.8 cm)

Duct:6.4"H x 3.0"W x 8.7"D (16.3 x 7.7 x 22.2 cm)

Duct probe:1 1/16″ (2.7 cm)diameter

Weight:

Wall:0.44 lb (0.2 Kg)

Duct:0.7 lb (0.32 Kg)

Approvals:CSA, RoHs, CE

Warranty:1 year

Certifications