Badger Meter Flow Monitor 3000 Series

Badger Meter Flow Monitor

 

The Badger Meter 3000 Series flow monitor is an economical, full-featured, compact unit designed for flow measurement applications. Outputs include one mechanical relay and one solid state pulse output, both featuring unit/pulse and set-point control independently based on flow or total readings. An analog 4-20 mA or 0-20 mA output is provided and USB, RS-485 Modbus, and BACnet/MSTP provide high-level communication. A two-line by 16-character, 3/8" high backlit LCD display is configured by the user to display flow rate and flow total. Custom units can be created during field setup. The flow sensor input features flexible scaling options and signal type selections that permit the use of most Data Industrial flow sensors, or other frequency (sine/pulse) or linear devices.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
3000-0-0 FLOW MONITOR,2 PULSE OUTS,PANEL MNT INFO1,993.491,594.79
3000-0-1 FLOW MONITOR,2 PULSE OUTS,WALL MNT In Stock2,323.891,859.11
3000-10 FLOW MONITOR,2 PULSE OUTS W/ANALOG OUT,PANEL MNT INFO2,426.641,941.31
3000-11 FLOW MONITOR,2 PULSE OUTS W/ANALOG OUT,WALL MNT INFO2,669.692,135.75
3100-0-0 DUAL FLOW MON, 2 PULSE, 1 ANA, 4 RELAY, 12-24V INFO3,127.652,502.12
3100-1-0 DUAL FLOW MON , 2 PULSE, 1 ANA, 4 RELAY, 120-240V INFO3,090.102,472.08
37003 ENCLOSURE FOR 1500 SERIES FLOW MONITOR INFO340.43272.34

Accessories

No accessories found
Features
  • One mechanical relay and one solid state relay output
  • Optional 0/4-20 mA output
  • USB, RS-485, Modbus, and BACnet/MSTP all in one unit
  • Menu-driven programming or Windows based programming
  • NEMA 4X rated
  • Two-line x 16-character display
  • Password restricted access
  • Non-volatile memory
Specifications

Supply Voltage:12-24 VAC/VDC

Supply Current:280 mA @ 24 VDC, 5 VA @ 24 VAC

Input:Data Industrial flow sensor or other frequency (sine/pulse) device

Maximum Output Impedance mA:1 kΩ maximum load @ 24 VDC (sinking); 600Ω maximum load (sourcing)

Output:Solid state pulse output rated at 1A @ 30 VAC or 35 VDC; closed 0.5Ω @ 1A; open >10 MΩ

Relay Output:Relay and pulse output are fully functional as either totalizing or setpoint outputs

Relay Output Rating:5A @ 120 VAC or 30 VDC resistive; 1A @ 120 VAC or 30 VDC inductive

Analog Output:4-20 mA, 0-20 mA range, isolated (sinking or sourcing); loop powered (sinking) output 30 VDC @ 0 mA maximum, 3 VDC @ 20 mA minimum; self powered (sourcing) output with 600Ω maximum load

Pulse Rate:1 pulse per 1.0000000 to 99999999 units; any predefined or custom unit can be used for flow totalizing; contact time 1 to 9999 milliseconds

Setpoints:Flow rate alarm setpoint available

Communication Interface:USB 2.0A to mini-B 5-pin cable required, provides access to all programming and operation features via Windows hyper-terminal

Communication Protocol:RS485 supports Modbus and BACnet/MSTP

Display:Backlit LCD, 16 characters/line, 0.31"H (0.79 cm), two lines

Engineering Units:Flow in GPM, gal/sec, gal/hr, Mgal/day, LPS, LPM, ft3/sec, ft3/min, ft3/hr, m3/sec, m3/min, m3/hr, acre-ft/sec, acre-ft/min, acre-ft/hr, bbl/sec, bbl/min, bbl/hr; Total in Mgal, liters, ft3, m3 acre-ft, bbl; or field-programmed custom

Operating Temperature:-4° to 158℉ (-20° to 70℃)

Enclosure Rating:NEMA 4X

Dimensions:

 :Panel Mount 3.6" H x 3.6" W x 3.2" D (9.1 x 9.1 x 6.3 cm)

 :Wall Mount 4.8" H x 4.8" W x 3.6" D (12.2 x 12.2 x 9.2 cm)

Weight:

 :Panel Mount 0.8 lb (0.34 kg)

 :Wall Mount 1.2 lb (0.54 kg)

Approvals:CE

Warranty:1 year

Certifications