Accuracy:
Humidity:2% (30% to 95%)
Temperature (EHRHT): ±0.5°F (±0.3°C)
Supply Voltage:24 VDC ±20% (loop powered)
Signal Output:4-20 mA
Maximum Output :
Impedance: 700Ω @ 24 VDC
Measurement Range:
Humidity: 0% to 100%
Temperature: -20° to 140℉ (-29° to 60℃)
Sensing Technology:
Humidity:Bulk polymer resistive
Temperature:Platinum 1000Ω 385 RTD (EHRHT)
:Type III 10 kΩ
Adjustments:
Zero:±20%
Span:±10%
Sensitivity: 0.1% RH
Operating Temperature:-4° to 129°F (-20° to 54°C)
Enclosure Rating:Epoxy-hardened waterproof case Cover: Stainless steel
Wiring Terminations:Flying leads
Weight: 0.75 lb (0.34 kg)
Warranty: 1 year