Zone and FCU Communicating Thermostat (BACnet, LON, N2) VT7200, VT7300 Communicating

Zone and FCU Communicating Thermostat (BACnet, LON, N2)

 

The Viconics VT7200 Zone thermostats are digital-display, heating / cooling, with outputs for two-position, floating, and proportional terminal unit control. They are ideal for baseboard heat, unit heaters, radiant panels, reheat, or VAV box (pressure-dependent) control. VT7300 Fan Coil Unit (FCU) thermostats are digital-display, heating / cooling, with outputs for two-position, floating, or proportional control. In addition, they include multi-speed fan relays for high, medium, and low fan speed control. Both thermostats offer remote temperature sensor and remote digital inputs configured for night setback, filter alarm, motion sensor, door/window switch, or service indication. All models offer standard BACnet or LON open-protocol communications.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
VT7200C5000W T-STAT/ZONE/W/2 FLTG CTRL W/REHEATINFO506.00283.36
VT7200C5031B T-STAT/BNET/1H/1C ZONE /ON/OFF/FLTG/NO FN/BLNK CVRIn Stock484.00271.04
VT7200F5031B T-STAT/BNET/1H/1C ZONE /2/0-10V PROP/NO FN/BLNKIn Stock572.00320.32
VT7300A5031B FCOIL COMMERCIAL 2 DIGITAL W/1 AUX W/ BA/BLNK CVRINFO709.00397.04
VT7300C5031P T-STAT/ON/OFF/OR/2/FLTG/CTRL/W/REHEAT/ZIGPROINFO708.92397.00
VT7305C5031B T-STAT/BNET/1H/1C FNCOIL /ON/OFF/FLTG/3SPDIn Stock630.00352.80
VT7350C5031B T-STAT/FCOIL COMMERCIAL 2 FLTG W/1 AUXW W/RH BAIn Stock694.00388.64
VT7350F5000 T-STAT/FCOIL COMMERCIAL 2 ANALOG W/1 AUXW/ W/RHINFO436.00244.16
VT7350F5031B T-STAT/FCOIL COMMERCIAL 2 ANALOG W/1 AUXW W/RHINFO734.00411.04
VT7355C5000B T-STAT/FCOIL HOTEL 2 FLTG W/1 AUXW W/RH BACNETINFO706.00395.36
VT7355C5031B T-STAT/BNET1H/1C FNCL /ON/OFF/FLTG/3SPDFN/INFO636.00356.16
VT7355F5031B T-STAT/BNET1H/1C FNCL /2/0-10V PROP/3S FN/In Stock861.00482.16

Accessories

No accessories found
Features
  • BACnet or LON communication models
  • Stand-alone operation on communication loss
  • Two-position, floating, or proportional models
  • Remote room sensor option
  • Adjustable deadband
  • Single setpoint adjustment
  • Setpoint range limits (heating and cooling)
  • Three configurable inputs for any of: night setback, setback override, motion sensor, door or window switch, filter alarm, service advisory, heat/cool changeover ℉/℃ (configurable)
  • Display offset
  • Adjustable temporary occupied time
  • Heat, cool, and reheat time base outputs are configurable
  • Direct or reverse acting (proportional models)
  • Keypad lockout functions
  • Dehumidification control models
  • Three-speed fan control (FCU model)
  • Selectable system control (FCU model)
  • PIR cover sensor (Optional)
Specifications

Supply Voltage:19-30 VAC, 50/60 Hz

Accuracy :Temperature, ±0.9℉ (±0.5℃)

 :VT7350C50xx, VT7350F50x Dehumidification, ±5% RH from 20% to 80% RH

Control Outputs:See terminal designation table

 :VT7200C50xx 5 triacs (H/C, 2-position or floating control)

 :

 :VT7200F50xx 1 triac, 2 analog outputs (H/C proportional 0 to 10 VDC)

 :VT7300C50xx, VT7350C50xx 3 relays (fan), 5 triacs (H/C, 2-position or floating control)

 :VT7300F50xx, VT7350F50xx 3 relays (fan), 1 triac, 2 analog outputs (H/C proportional 0 to 10 VDC)

 :Triacs and relays 30 VAC, 1A, 3A inrush

 :Analog outputs 0-10 VDC, 2KΩ minimum impedance, direct or reverse acting

Auxiliary Inputs:2 digital inputs, 1 universal input, 1 remote sensor

 :Configurable as Service/status reminders

 :Door/window/motion sensor switch

 :Filter alarm

 :Central night setback clock

 :Remote occupied override switch

 :Heat/Cool changeover, contact or sensor

Digital Inputs:Dry contact

Universal Input:Dry contact or 10K Type 2 Model 24 thermistor

Display:Two line backlit LCD, ±0.2℉ (±0.1℃)

Thermostat Type:Zone (VT7200) or FCU (VT7300)

Cover Controls:

 :Zone Models Up/down/override buttons

 :Heat/Cool “on” LEDs

 :FCU Models Up/down/℃-or-℉/fan/mode buttons

 :Fan/Heat/Cool “on” LEDs

Remote Sensor:Thermistor, 10K Type 2 Model 24

Control Type:Proportional plus integral (PI)

Proportional Band:Heating and cooling, 2℉ (1.1℃)

Floating Time Base:Adjustable, 0.5 to 9 minutes

Cycles Per Hour:Adjustable 3 to 8

Override Timer:0 to 24 hours, 1-hour increments, pushbutton reset

Sensor Offset:Adjustable ±5℉ (±2.5℃), ±15% RH (humidity models)

Deadband:Adjustable 2° to 5℉ (1° to 2.5℃)

Setpoint:Adjusted depending on heating or cooling mode, heating and cooling setpoints are changed simultaneously with respect to the deadband

 :Cooling limits 54° to 100℉ (12℃ to 37.7℃)

 :Heating limits 40° to 90℉ (4.5° to 32℃)

Keypad Lockout:Selectable system/fan/unoccupied

System Setting:O=off, H=heating, C=cooling, A=automatic changeover

 :(FCU models) O/C, O/H, O/A/H/C, H/O/C

Fan Setting:L=low, M=medium, H=high, A=auto

 :(FCU models) L/M/H, L/H, L/M/H/A, L/H/A, On/A

Wiring:18 AWG maximum, 22 AWG recommended

Color:White

Mounting:Standard vertical, 2″ x 4″ box

Operating Temperature:32° to 122℉ (0° to 50℃)

Operating Humidity:0 to 95% RH (non-condensing)

Enclosure Rating:UL FR1, flame retardant plastic

Dimensions:4.94″H x 3.38″W x 1.13″D

 :(12.5 x 8.6 x 2.9 cm)

Weight:0.75 lb (0.34 kg)

Approvals:UL Listed File #E234137, cULus, CE, LonMark

Warranty:1 year

Certifications