Supply Voltage:24 VAC ±10%, half-wave; or 24 VDC ±10%
Supply Current:50 mA @ 24 VAC; 25 mA maximum @ 24 VDC
Accuracy:±1%
Input:0.5-20 mA or 0.75-15 VDC, jumper selectable
Input Impedance:250Ω (mA input); 10 kΩ (VDC input)
Output:One SPDT relay, factory set at 12 mA, 9 VDC; adjustable via setpoint potentiometer
Relay Differential:Factory set at 0.5 mA or 0.375V, adjustable 0.2-2V or 0.25-3 mA
Relay Output :5A @ 120 VAC
Wiring Terminations:Screw terminals
Time Constant:30 seconds, jumper enabled
Operating Temperature:32° to 158℉ (0° to 70℃)
Operating Humidity:5% to 95% RH (non-condensing)
Dimensions:
:UCS-121 3.3"H x 1.5"W x 1.3"D (8.2 x 3.8 x 3.2 cm)
:UCS-121-H 4.0"H x 2.3"W x 1.8"D (10.2 x 5.7 x 4.4 cm)
Weight:0.2 lb (0.09 kg) without enclosure; 0.3 lb (0.14 kg) with enclosure
Approvals:RoHS
Warranty:1 year