Universal Resistance Transducer GT-ARES Series

Universal Resistance Transducer

 

The Greystone Energy Systems GT-ARES Series universal resistance transducer provides a precision resistance output for DDC control of electric actuators or other electronic devices that operate from a variable resistive circuit. Various selectable analog inputs are available, and the transducer may be powered from 24 VAC or 24 VDC. The GT-ARES is furnished with snap-track for easy mounting.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
GT-ARES-1000 ANALOG TO 1000 OHM RESISTANCE MODULEINFO448.00224.00
GT-ARES-135 ANALOG TO 135 OHM RESISTANCE MODULEINFO448.00224.00
GT-ARES-2000 ANALOG TO 2000 OHM RESISTANCE MODULEINFO448.00224.00
GT-ARES-270 ANALOG TO 270 OHM RESISTANCE MODULEINFO448.00224.00
GT-ARES-500 ANALOG TO 500 OHM RESISTANCE MODULEINFO448.00224.00

Accessories

No accessories found
Features
  • Field-selectable input ranges
  • Several resistance output ranges
  • LED power indicator
  • Regulated 20 VDC power output
  • Compact and economical
  • Snap track mounted
Specifications

Supply Voltage:23-30 VDC, 22-27 VAC half-wave rectified

Input: 0-20, and 4-20 mA; 0-5, 0-10, 0-15, 1-5, 2-10, 3-15 VDC

Input Impedance:250Ω

Wiring Terminations:Screw terminal block 14-22 AWG

Accuracy:±5.0%

Operating Temperature:32° to 122℉ (0° to 50℃)

Operating Humidity:5 to 95% RH, non-condensing

Enclosure: Snap track mounting; 4.6″L x 3.3″W (11.6 x 8.4 cm)

Approvals: CE, RoHS

Weight: 0.3 lb (0.1 kg)

Warranty: 5 years

Download Additional Data

document   GT-ARES DATASHEET 2016