Input:0.5-9 VDC, 0.25-9.5 VDC, 4-20 mA
Input Impedance:Voltage models: 1000Ω min.
Current models: 350Ω max.:
Wiring Terminations:Terminal block for 18-24 AWG wire
Action:Proportional, direct acting
Air Capacity:Low volume models: 12.3 ml/s (45 scim) max. (value specified for dead-ended loads or with controlled devices/applications with a max. air consumption of 2.7 ml/s [10 scim])
High volume models: 437 ml/s (1600 scim) max.:
Air Connections:Barbed fittings for 5/32 or 1/4″ O.D. polytubing
Air Consumption:Low and high-volume models: 12.3 ml/s (45 scim) max.
Linearity:5% maximum of output span between 3-15 psig (21-103 kPa)
Hysteresis:1.4 kPa typical
Materials Of Construction:Body: Polysulphone
Case and cover: UL94 V-O rated polycarbonate:
Enclosure protection: IP 42 according to DIN 40 050 AND IEC 144:
Air connections: Brass:
Output:1-18 psig (7-126 kPa); low volume, non-relay, 0.5-19 psig (3.5-133 kPa), high volume, relay, 3-15 psig (21-105 kPa), low volume, non-relay, 3-15 psig (21-105 kPa), high volume, relay
Adjustments:Voltage models: 20 VDC max. input; span adjustable from 7.5-15 VDC
Current models: 30 mA DC max. input; span adjustable from 10-20 mADC:
All models: Output can be shifted ±9 psig (63 kPa) using zero adjustment screw:
Operating Temperature:41° to 122℉ (5° to 50℃)
Operating Humidity:10 to 90% RH, non-condensing
Mounting:Surface mounted or installed on a valve pneumatic actuator
Pressure:18 to 25 psig (126 to 175 kPa); nominal 20 psig (140 kPa); air supply must be clean, dry, and oil free
Sensitivity:0.3 psig/psig (0.3kPa/kPa)
Temperature Coefficient:0.64 kPa/℃
Approvals:CE
Weight:
8000-1/-3:0.5 lb (0.23 kg)
8000-2/-4:0.6 lb (0.27 kg)