Supply Voltage:19-30 VAC, 50/60 Hz
Supply VA:6 VA
Accuracy :Temperature, ±0.9℉ (±0.5℃)
Digital Inputs:Dry contact
Universal Input:Dry contact or 10K Type 2 Model 24 thermistor
Display:Two line backlit LCD, ±0.2℉ (±0.1℃)
Cover Controls:
:Zone Models Up/down/override buttons
:Heat/Cool “on” LEDs
:FCU Models Up/down/℃-or-℉/fan/mode buttons
:Fan/Heat/Cool “on” LEDs
Remote Sensor:Thermistor, 10K Type 2 Model 24
Control Type:Proportional plus integral (PI)
Cycles Per Hour:Adjustable
Setpoint:Adjusted depending on heating or cooling mode, heating and cooling setpoints are changed simultaneously with respect to the deadband
:Cooling limits 54° to 100℉ (12℃ to 37.7℃)
:Heating limits 40° to 90℉ (4.5° to 32℃)
Keypad Lockout:Selectable system/fan/unoccupied
System Setting:O=off, H=heating, C=cooling, A=automatic changeover
Fan Setting:L=low, M=medium, H=high, A=auto
Wiring:16-24 AWG, 22 AWG recommended
Color:White or Silver
Mounting:Standard vertical, 2″ x 4″ box
Operating Temperature:32° to 122℉ (0° to 50℃)
Operating Humidity:0 to 95% RH (non-condensing)
Enclosure Rating:UL FR1, flame retardant plastic
Dimensions:4.72″H x 3.38″W x 1.00″D
:(12.0 x 8.6 x 2.5 cm)
Weight:0.75 lb (0.34 kg)
Approvals:UL Listed File #E234137, cULus, CE
Warranty:1 year