Suppy Voltage:24 VAC
System Type:4 heat/2 cool heat pump and up to 3 heat/2 cool conventional
Sensor Type:
:Temperature Onboard 20kΩ NTC
:Humidity Capacitive
Communication:RedLINK devices
Baud Rate:900 MHz frequency range
Analog Input:EIM
:2 Universal inputs, temperature or dry contact selectable (not available with single- piece thermostat)
Output:
:EIM 7
:Standalone 6 (USB on some models)
Contact Rating:
:EIM terminals W-O/B, Y, W3-Aux2, A-L/A Maximum Current 1.0A,
:EIM terminals G, U1, U2, U3 Maximum Current 0.5A
:EIM terminals W2-Aux1, Y2 Maximum Current 0.6A
Temperature Sensor Accuracy:± 1.5° at 70℉ (0.75° at 21℃)
Temperature Setting Range :
:Heating 40° to 90℉ (4.5° to 32℃)
:Cooling 50° to 99℉ (10° to 37℃)
Operating Temperature:
:Thermostat 32° to 120℉ (0° to 48.9℃)
:EIM -40° to 165℉ (-40° to 73.8℃)
Operating Humidity:
:Thermostat 5% to 90% condensing,
:EIM 5% to 95% non-condensing
Dimensions:
:Thermostat
:Prestige IAQ 4-1/2″W x 3-1/2″H x 7/8″D (11.5 x 8.9 x 2.2 cm)
:Prestige 2.0 6-13/16″W x 3-7/8″H x 1-7/16″D (17.3 x 9.9 x 3.6 cm)
:EIM 9.34″H X 4.83″W X 1.6″D (23.7 x 12.3 x 4.1 cm)
Measurement Range:Building material and content dependent
Weight:2.0 lbs (maximum item)
Approvals:This device complies with Part 15 of the FCC Rules. (15.19, 15.21, 15.105)
RoHS Statement:Yes
Warranty:5 years (excludes batteries)