CP-8552 | Greystone Energy Systems | Transducers
4-20MA CURRENT/6 TO 9VDC/0 TO 10VDC XDUCER
Brand:Greystone Energy Systems
MPN:CP-8552
SKU:CP-8552
List Price:
$341.00
Today's Price:
$177.32
product specifications
Mount
DIN Rail
Output
Pneumatic
Supply Voltage
20-30 VAC, 50/60 Hz, 24-30 VDC
Type
Electro-Pneumatic
Output Signal
3-15 psig, 21-103 kPa
Input
Analog
Input Signal
4-20 mA, 0-10 VDC, 6-9 VDC
product series specifications
- Supply Voltage:
- :
- CP-8551 None, 4-20 mA loop powered
- :
- CP-8552, -8511 20 to 30 VAC, 50/60 Hz or 24 to 30 VDC
- Supply VA:
- 3.9 VA (CP-8552)
- Supply Watts:
- :
- CP-8552 1.6 W maximum
- :
- CP-8511 3.8 W
- Input:
- :
- CP-8551 4-20 mA
- :
- CP-8552 4-20 mA, 0-10 VDC, 6-9 VDC, jumper selectable
- :
- CP-8511 4-20 mA, 1-5 mA, 6-9 VDC, 1-5 VDC, 0-10 VDC, 1-11 VDC, 2-10 VDC, jumper selectable
- Input Impedance:
- :
- CP-8551 550Ω
- :
- CP-8552 550Ω (current input); >10 kΩ (voltage input)
- :
- CP-8511 250Ω @ 4-20 mA; 1000Ω @ 1-5 mA; >10 kΩ for voltage inputs
- Output:
- 3-15 psig (21-103 kPa)
- Output Voltage:
- 20 VDC auxiliary output (CP-8511 only), 50 mA maximum
- Wiring Terminations:
- Screw terminals for 16 to 22 AWG wire
- Action:
- :
- CP-8551, -8552 Direct acting
- :
- CP-8511 Direct or reverse acting, jumper selectable
- Air Capacity:
- 550 scim (150 ml/s)
- Air Connections:
- Barbed fittings for 1/4" OD tubing
- Air Consumption:
- 0.012 scfm (5.66 ml/s) @ 20 psig (138 kPa) supply
- Maximum Pressure:
- 30 psig (207 kPa) maximum
- Media Compatibility:
- Clean, dry air; 20 psig nominal supply pressure
- Linearity:
- ± 1% of span @ 75‚Ñâ (24‚ÑÉ)
- Hysteresis:
- 0.75% of span @ 75‚Ñâ (24‚ÑÉ)
- Adjustments:
- :
- CP-8552 Adjustable start point and span potentiometers for voltage input
- :
- CP-8511 Field adjustable zero potentiometer
- Manual Override:
- Auto/manual switch enables output override using a manual output potentiometer, LED goes off when in Manual mode (CP-8511 only)
- Feedback:
- Auto/manual feedback provided by isolated open collector output transistor (OC, OE) (CP-8511 only)
- Operating Temperature:
- 32° to 140‚Ñâ (0° to 60‚ÑÉ)
- Operating Humidity:
- 5 to 95% RH, non-condensing
- Mounting:
- Vertical, within 5°
- Enclosure Rating:
- NEMA 1
- Dimensions:
- :
- CP-8551, -8552 4.6"H x 2.8"W x 2.6"D (11.8 x 7.1 x 6.8 cm)
- :
- CP-8511 4.6"H x 5.0"W x 2.6"D (11.8 x 12.7 x 6.8 cm)
- Weight:
- :
- CP-8551, -8552 0.4 lb (0.2 kg)
- :
- CP-8511 0.8 lb (0.4 kg)
- Approvals:
- UL File #E9429; CSA, C22.2 No. 24-93; CE, EMC Directive 89/336/EEC, low voltage directive 72/23/EEC
- Warranty:
- 1 year
product series features
- Panel or DIN-rail mount for quick snap-on installation
- High accuracy and low hysteresis for precise control
- Long-term, driftless operation with high repeatability for long life and high performance
- Low air consumption to save energy
- High airflow capacity to handle large pneumatic components and long tubing runs
- Models with field-selectable inputs
- Integral 20 VDC auxiliary power supply, pressure gauge and manual override on CP-8511
more information & related documents
Series Description
The CP-8500 Series electronic/pneumatic transducers handle a wide variety of pneumatic valve and damper applications that require a 3-15 psig control signal from an electronic controller output. The CP-8551 electro pneumatic transducer is a basic two-wire loop-powered unit with 4-20 mA input. The CP-8552 transducer is a 3-wire unit with a jumper-selectable input for 4-20 mA, 6-9 VDC or 0-10 VDC. The CP-8511 pneumatic transducers have a variety of jumper-selectable inputs, a pressure gauge, manual override, and 20 VDC power output for auxiliary components.
Kele Description
4-20MA CURRENT/6 TO 9VDC/0 TO 10VDC XDUCER
Manufacturer
Greystone Energy Systems
Related Documents