BA/1K375-I-8-BB-TS | BAPI | Temperature Sensors & Transmitters

Immersion Temperature Sensor, 1K RTD 375, 8 Probe, BAPI-BOX Plastic Enclosure, IP66 rated, Terminal Strip Connection

Brand:BAPI

MPN:BA/1K375-I-8-BB-TS

SKU:BA/1K375I8BBTS

List Price:

$80.52

Today's Price:

$41.87



product specifications

Accessory

T81U-XR, T85U-XR, TCC-111, TCC-12, UR

Feature

Stainless Steel Well

Application

Hydronic HVAC

Housing Material

Poly

Housing Rating

NEMA 4, IP66

Output

Resistance

Probe Length

8 in

Sensor Element

1K Platinum RTD 375

Type

RTD

product series specifications

Accuracy: Thermistor: ±0.36°F (0.2°C); RTD: ±0.55°F (0.30°C)

Sensor Type: Thermistor: 10 k? Type II & III; RTD: 100?, 1000?, 385 curve; 1000?, 375 curve

Temperature Range: 32° to 158°F (-0° to 70°C)

Stability: Thermistor: <0.036°F (0.02°C) per year; RTD: 0.14°C with 6,000 continuous hours at 400°C

Heat Dissipation: 2.7 mW/°C (power need to raise the temperature 1°C), 0.4°C/mW at 0°C

Enclosure Rating:

JB: NEMA 1, 2" x 4" J-box with 1/2" knockouts

BB: BB2: BB4: NEMA 1, BAPI Box 4- IP20 nylon & plastic

WP: NEMA 3R Aluminum

Mounting: Directly to pipe

Wiring Terminations: 22 AWG wire, etched teflon leads

Weight: I2: 0.65 lb (0.29 Kg) I4 & I8: 0.8 lb (0.36 Kg)

Approvals: CE, RoHS

Warranty: Lifetime

product series features

  • Several enclosure styles with mounting tabs
  • Probe lengths: 2 in, 4 in and 8 in
  • Lifetime limited sensor warranty

more information & related documents

Series Description

The BAPI BA Series Thermistor and RTD Immersion Sensors are designed specifically for HVAC systems. They come in thermistor and RTD sensors and feature double encapsulated sensor etched Teflon leadwires to create a watertight package that can perform in the real world.

Kele Description

TEMP SENSOR, IMMERS, 1K RTD 375, 8.00" PROBE, POLY ENCL

Manufacturer

BAPI

Related Documents