A/1K-3W-DO-12"-6'-CL2P | ACI | Temperature Sensors & Transmitters
Platinum RTD, Duct, 1,000 Ω RTD (3-wire), 12", No Box, Flange Only, 6 ft 2 Conductor Plenum Rated Cable
Manufacturer:ACI
MPN:A/1K-3W-DO-12"-6'-CL2P
SKU:A/1K3WDO126CL2P
availability:Usually Ships in Less Than 8 Business Days
add to cart

product specifications
Accessory
TT100-0100-BO-1||TT100-0100-BO-2||TT100-0100-BO-4||TT1K-0100-BO-1||TT1K-0100-BO-2||TT1K-0100-BO-4||UR||F-1000-331
Application
Duct Temperature||Air Handling Unit
Description
Platinum RTD, Duct, 1,000 Ω RTD (3-wire), 12", No Box, Flange Only, 6 ft 2 Conductor Plenum Rated Cable
Feature
Plenum Cable
Lead Length
6 ft
Probe Length
12.00"
Sensor Element
1K RTD 385
Short Description
TEMP SENSOR, DUCT, 1K RTD 385, 12.00" PROBE, NO ENCL
Type
RTD
product family features
- Five-year warranty
- Wide selection of thermistor or RTD curves
- Stainless steel probes
more information & related documents
Family Description
The ACI Duct Series Thermistor and RTD Sensors are designed specifically for HVAC system temperature control. The duct sensors come in thermistor and RTD sensor curves compatible with most BAS systems available today. Duct sensors come with a foam-backed handy box and 8″ probe. The A/*D Duct Sensor should be mounted close to the center of the duct and penetrate through any duct insulation at least 1″ (2.5 cm) into the airflow. The probes are sensitive within 1″ of the tip and insert through a 3/8″ (1 cm) hole. Use standard metal screws to secure to the duct.
Kele Description
TEMP SENSOR, DUCT, 1K RTD 385, 12.00" PROBE, NO ENCL
Manufacturer
ACI