product family specifications
Device Operation
Supply Voltage
Most modules powered from BA/RCV receiver
VOM, ROM
Powered from reciever bus
RYOx, SOM
Powered from reciever bus
COM
9-36 VDC from current loop
Output
RS485 bus to a maximum of 127 ″Output Modules″
BA/VOM-xx
0-5V or 0-10V @10KO
BA/COM-xx
4-20mA, 750O @24VDC
BA/SOM-xx
0-5V or 0-10V @10KO, or Resistance 0-75K
BA/ROM-xxx
Thermistor (10K-2, 10K-3, 20K)
BA/RYOM
Momentary, Triac, 40V AC/DC, 150mA, 1µA leakage
BA/RYOL
Latching, Triac, 40V AC/DC, 150mA, 1µA leakage
Indication
LED blinks on each reception
A/D resolution
10 bit, 1024 counts″
Mounting
DIN rail or 2 screws to back plane
Output modules plug into the right side of receiver
and/or other output modules
Wiring
2 field terminals, 22-16 AWG
RS485 Comm. trunk 6 terminals or plug
Operating Temperature
32 to 140℉ (0 to 60℃)
Operating Humidity
5-95% RH non-condensing
Construction
ABS Plastic, UL94V-0
Enclosure Rating
Indoor, NEMA 1
Dimensions
2.75″H x 2.34″W x 1.2″D, (7.0 x 5.9 x 3.0 cm)
Weight
0.3 lb (0.14 Kg)
Warranty
2 year
Radio/Radio Receiver Interface
Update Interval
Updates on each reception
Lost Comm. Fail Safe
If no reception >15 minutes modules fail safe
BA/VOM-xx
℉ Fails low and %RH Fails high
BA/COM-xx
℉ Fails low and %RH Fails high
BA/SOM-xx
℉ Fails low
BA/ROM-xx
℉ Fails low
BA/RYOM
Fails to the normal condition per order (NO or NC)
BA/RYOL
Fails to the normal condition per order (NO or NC)
Programming
Push button on ″Transmitter/Output Module″ simultaneously
Approvals
RoHS
product family features
- Provide BAS point wiring
- 127 modules per system
- Thermistor simulation for temperature
- 0-10 VDC, 0-5 VDC, or 4-20 mA signals
- Solid-state contacts
- Built-in fail-safe on signal loss
- Snap-track and DIN rail mounting
more information & related documents
Family Description
The BAPI BA/ROM, VOM, COM, and RYOM wireless system output modules are specifically designed to connect to any BA/RCV receiver and communicate over an RS485 communication trunk to generate standard output signals for any BAS system. A total of 127 modules may be interspersed on the RS485 trunk. Each will output a signal representative of its assigned remotely located wireless transmitter. Each module may be powered from the receiver power bus, or individually, based on overall system power requirements. The BAPI BA/ROM thermistor simulation output module converts a wireless transmitter temperature signal according to a standard thermistor curve. The three standard curves are 10 KΩ Type 3, a 10 KΩ Type 2, with a resistance temperature response of 35° to 120°F (1° to 50°C) and a 20 K thermister curve with response of 50° to 120℉ (12° to 50℃). The BAPI BA/VOM voltage output module converts a wireless transmitter temperature signal to a standard voltage signal. The two standard voltage outputs are 0-5 VDC and 0-10 VDC, with voltage temperature responses based on individual models. The BAPI BA/COM current output module converts a wireless transmitter temperature signal to a standard 4-20 mA current signal. The 4-20 mA current is typical of a loop powered (9-36 VDC) device with current temperature responses based on individual models. The BAPI BA/RYOM digital output module converts the pushbutton on a wireless room temperature transmitter to a solid-state relay momentary closure for AC or DC voltages (5 second momentary actuation). NO or NC solid-state contacts are available, based on individual models. The BAPI BA/RYOL digital output module converts the BA/WDI digital input transmitter signal to a latching relay output. NO or NC fail safe contacts are available, based on individual models. The BAPI BA/SOM setpoint output module converts the setpoint data received to a resistance or voltage output.