product specifications

Accessory

DCP-1.5-W, DCPA-1.2, 691-K0A

Feature

Transmitter

Accuracy

±2.00%

Application

Wet Bulb, Energy Management Systems, Hospital, Lab, Refrigeration Control, Pharmacy, Economizer, Supermarkets, Condensation Prevention

Housing Material

Poly

Housing Rating

IP42

Wet Bulb Accuracy

±3°F, 1.7°C

Wet Bulb Range

0° to 100°F, -17.8° to 37.8°C

Output Signal

4-20 mA

Mounting Location

OSA

Power Requirements

24 VAC/VDC

product series specifications

    Accuracy:
    Enthalpy:
  • ±2 BTU/lb
    Dew Point:
  • ±1.8°F (±1°C)
    Wet Bulb:
  • ±3.24°F (±1.8°C)
    Dry Bulb:
  • ±0.5°F (±0.9°C)
    Supply Voltage:
  • 12-30 VDC, 100 mA
    Signal Output:
  • Field selectable: 4-20 mA (700Œ© max load), 0-5 V, or 0-10 V Humidity and dry bulb temperature
    Measurement Range:
    Dew Point:
    Duct/OSA:
  • -20° to 120°F (-28.8° to 49°C)
    Space:
  • 40° to 90°F (4.4° to 32.2°C)
    Enthalpy:
    Space/Duct/OSA:
  • 0-50 BTU/lb
    Wet Bulb:
    Duct/OSA:
  • 0° to 100°F (-17.8° to 37.8°C)
    Space:
  • 40° to 90°F (4.4° to 32.2°C)
    Dry Bulb:
    Duct/OSA:
  • -20° to 120°F (-28.8° to 49°C)
    Space :
  • 40° to 90°F (4.4° to 32.2°C)
    Sensing Technology:
  • Capacitive and replaceable
    Operating Temperature:
  • -40° to 140°F (-40° to 60°C)
    Operating Humidity:
  • 0 to 99% RH, non-condensing
    Aprrovals:
  • CE, RoHs
    Weight:
    Room:
  • 0.34 lb (0.15 Kg)
    Duct:
  • 0.96 lb (0.44 Kg)
    OSA:
  • 1.22 lb (0.55 Kg)
    Warranty:
  • 1 year

product series features

  • Dew point accuracy of ±1.8 degrees F (±1 degrees C) over the specified range
  • Enthalpy accuracy of ±2 BTU/lb over specified range
  • Wet bulb accuracy of ±3 degrees F over the specified range
  • Dry bulb accuracy of ±.05 degrees F (±0.9 degrees C)over the specified range
  • Two 4-20 mA output signals
  • Microprocessor-based signal processing
  • Weather resistant duct/OSA mounting
  • Temperature compensated

more information & related documents

Series Description

The Amphenol Advanced Sensors Model DP4 Dew Point, WB4 Wet Bulb, and EN4 Enthalpy Transmitters are rugged and compact. Each transmitter uses a capacitive RH sensor and an RTD temperature sensor to compute the dew point, wet bulb, or enthalpy for building automation and process applications. Two linear outputs provide a 4-20mA signal for dew point, wet bulb, or enthalpy, and a 4-20 mA signal for dry bulb. These transmitters are proven performers in Building Automation Systems, BAS, and HVAC applications.