TCI-W13-U-H-W25 | Vector Controls Ltd | Humidity
Wall Mounted Universal Controller, 1 Loop, PI-Controller, 1 UI, 2 AO, 1 DO (Relay), Temperature and Internal Humidity Sensor 3% Accuracy, Dehumidification
Brand:Vector Controls Ltd
MPN:TCI-W13-U-H-W25
SKU:TCI-W13-U-H-W25
List Price:
$532.00
Today's Price:
$276.64
product specifications
Accessory
AES3-HT-A2, AES3-HT-A3, DCPA-1.2, DCP-1.5-W, UR
Accuracy
±3.00%
Application
Humidification, Dehumidification, Monitoring Indoor Space Humidity, Clean Rooms, Hospitals, Process Control, Laboratories,Museums, Schools, Office Buildings, Data Centers, ESD (Anti-Static) Control
Housing Material
Poly
Housing Rating
IP30
Display
LCD
Output Signal
4-20 mA
Mounting Location
Room
Power Requirements
24 VAC/VDC
product series specifications
- Accuracy:
- ±3% RH (20%-80%)(H models)
- Supply Voltage:
- 24 VAC ±10% 3 VA, 50-60 Hz; 24 VDC, 125 mA
- Signal Output:
- Analog:
- 0/2-10 VDC or 0/4-20 mA @250Ω
- Digital:
- 24 VAC/VDC @ 2 A
- Signal Input (U models):
- 13:
- 0/2-10 VDC or 0/4-20 mA @ 240Ω
- 23:
- 0/2-10 VDC or 0/4-20 mA @ 240Ω & 10kΩ Type II thermistor (24)
- Measurement Range:
- 0 to 100 % RH
- Operating Humidity:
- 0% to 95% non-condensing
- Operating Temperature:
- 32° to 122‚Ñâ (-25° to 50‚ÑÉ)
- Enclosure Rating:
- ABS Plastic
- Sensing Technology:
- Capacitive sensor
- Wiring Terminations:
- Terminal block (12 to 24 AWG)
- Dimensions:
- 4.4‚Ä= H x 2.9‚Ä= W x 1.8‚Ä= D (11.2 x 7.3 x 4.7 cm)
- Approvals:
- CE
- Weight:
- 13:
- 0.58 lb (0.26 Kg)
- 23:
- 0.6 LB (0.27 kG)
- Warranty:
- 2 years
product series features
- Humidification and dehumidification control
- External temperature input for set point setback
- Programmable user interface
- Optional time clock
- 2 analog outputs
- Easy to read display
more information & related documents
Series Description
The Vector Model TCI wall and duct proportional controller is designed for proportional control of humidification and dehumidification equipment in HVAC and energy management systems. The in.23 in. models comes with a time clock for advanced programming with 48 hour backup and the in.13 in. models do not. The in.H in. models have internal relative humidity sensors and the others without in.H in. in model number must use a remote relative humidity sensor (ordered separately) for RH measurement.
Kele Description
3% WALL MNT PROP HUMSTAT DISP DEHUMIDIFICATION
Manufacturer
Vector Controls Ltd
Related Documents