product family specifications

Power Supply

 15-30VDC/24VAC(1), 4W max, 160mA max.

Analog Outputs

 2 programmable outputs: 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable) 

 CO output scaling: 0-200ppm (default), 0-1000ppm (menu selectable) 

 NO2 output scaling: 0-10ppm (default), 0-30ppm (menu selectable) 

 Temperature output scaling: -20 to 85oC 

BACnet /Modbus

 Protocol RS-485: BACnet MS/TP, Modbus RTU, Modbus ASCII 

 Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200 

 

Fan Relay

 Fan relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection) 

 CO fan relay setpoint: 25ppm (default), 0-1000 ppm (menu selectable) 

 NO2 fan relay setpoint: 1ppm (default), 0-30ppm (menu selectable) 

 

Alarm Relay (Analog model only)  

 Alarm relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection) 

 CO alarm relay setpoint: 100ppm (default), 0-1000 ppm (menu selectable) 

 NO2 alarm relay setpoint: 3ppm (default), 0-30ppm (menu selectable) 

Display

 3-1/2 digit LCD: Indicates CO ppm, NO2 ppm (menu selectable)

LEDs

 Green, Yellow, Red: Green = Normal, Yellow = Relay, Red = Alarm 


 

Audible Alarm Exposure 

 85dB Piezo transducer: 30 minutes above alarm setpoint per UL2034 (menu selectable)

CO Sensor Performance

 Type: Electrochemical 

 Accuracy: ±5% of default range(2) ±5%of reading above menu selectable)

 Resolution: 1ppm 

 Certications: UL2034 Listed Component 

 Life expectancy: >7 years 

 Coverage Area: 5000-7500 square feet 

 

NOSensor Performance

 Type: Electrochemical 

 Accuracy: ±5% of default range(3) ±5% of default range(3) ±5%of reading above 20ppm 

 Resolution: 0.1ppm 

 Life expectancy: >7 years 

Coverage Area: 5000-7500 square feet 

Methane Sensor Performance

 Type: Catalytic 

 Detection Range: 0-50% LEL (Lower Explosive Limit) 

 Accuracy: 5% of range 

 Resolution: 1%LEL 

 Life expectancy: >5 years 

 Coverage Area: 5000 square feet 

 

Propane Sensor Performance

 Type: Catalytic 

 Detection Range: 0-50% LEL (Lower Explosive Limit) 

 Accuracy: 5% of range 

 Resolution: 1%LEL 

 Life expectancy: >5 years 

 Coverage Area: 5000-7500 square feet 

 

Operating Environment

 Temperature, continuous: -20 to 50oC 

 Humidity: 15-95% continuous, 0-95% intermittent 

 Max Elevation: 2000m 

 

Enclosure (Wall & Duct)

 Material: ABS/Polycarbonate 

 Dimensions: 4.0”h x 4.4”w x 2.1”d 

 Conduit Opening: Tapped 1/2” NPT 

 Rating: IP20 

Enclosure (Metal)

 Material & Enclosure Rating: Powder-coated steel/acrylic, NEMA 3R 

 Dimensions: 5.0”h x 4.3”w x 2.25”d 

 Opening: Dual air vents on the bottom of the enclosure 

 Mounting: Pre-drilled for 2x4” electrical box 

 Rating: IP20 

Approvals

 Compliance UL61010-1 Listed UL, cUL

 
Warranty

  7 years

product family features

  • Cost-effective dual gas sensing and control 
  • Flexibility of analog output model 
  • Versatility with BACnet/Modbus model 
  • High reliability reduces callbacks 
  • Easy to install 

more information & related documents

Family Description

Senva TG UL Series wall and duct sensors can be ordered as individual sensors or as any dual combination of CO / NO2 / CO2 / Methane / Propane / Hydrogen / Oxygen / H2S / Ammonia / Refrigerants sensor in a shared enclosure.   The analog output model features two outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost-effective coverage of large areas. The unit can also act as a stand-alone controller, utilizing the relay for exhaust fan operation, or the output for direct control of a VFD. The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display, and audible alarm.