EFAMS-DI-PL-30-8

EFAMS-DI-PL-30-8 | Ruskin Manufacturing | Flow

AIR MONITORING STATION, DUAL INLET, STD. DEN., PLEN FAN BCKWRD INCL/CRVE/ARFL, 30FT CABLE, NO XFMR

Manufacturer:Ruskin Manufacturing

MPN:EFAMS-DI-PL-30-8

SKU:EFAMS-DI-PL-30-8

list price:

3,760.58

1,880.29



(login for better pricing)
USD

availability:Usually Ships in Less Than 10 Business Days

add to cart

arrow

product family specifications

SURFACE-MOUNT SENSOR ENCLOSURE

 Aerodynamically shaped, high impact ABS, with stainless sensor cap. U.L. 94 flame rated housing conforms to the inlet bell contour providing a low profile installation that reduces pressure drop, and saves energy

SENSOR DISTRIBUTION

 Two sensor circuits mounted opposite of each other

SENSOR CIRCUIT (two standard, up to four per fan location)

 Two hermetically sealed, heated thermistors 

 Two hermetically sealed, ambient thermistors

SENSOR ACCURACY

 Airflow: ±3%. 

 Temperature: ±0.10° F (0.056°C)

SENSOR RANGES

 Airflow Rate: 0-10,000 FPM

 Temperature: - 25° F to 140° F (-32°C to 60°C)

 Humidity: 0-99% RH, non-condensing

ROUTER UNIT (one per fan location)

 One microprocessor based multiplexer circuit

 Sensor/communications circuit 

 All circuits encapsulated in electronic potting compound

COMMUNICATION CABLE

 UL Plenum rated shielded CAT5e network cable (10' [3.05m] standard). RJ-45 Connectors with   dust boot cover and gold plated pins. Digital interface between router and transmitter.

CONTROL TRANSMITTER

 Microprocessor based. 6" x 113/8" (152mm x 289mm) nominal control enclosure. 

 16x2 character LCD display (airflow, temperature & diagnostics). 

 Seamless "plug & play" connectivity to Router & 2-4 sensor circuits. 

 24VAC internally fused power supplied by others. 

 Velocity Output: Field selectable 4-20mA (Std.) or 2-10 VDC using 500 ohm resistor. 

 Temperature Output: Field selectable 4-20mA (Std.) or 2-10 VDC using 500 ohm resistor

OPERATING RANGE

 Temperature: -20° F to 120° F (-29° C to 49° C) 

 Humidity: 0-99% RH, non-condensing

POWER REQUIREMENT

 24 VAC transformer

product family features

 Includes a minimum of two sensors, a router and transmitter box with LCD display showing both temperature and air flow velocity or volume in either FPM, CFM or Meters per second or Liters per second.  
 Easily field configured for any size fan.  
 The transmitter box provides two isolate 4-20 mA analog linear signal outputs representing measured air flow and temperature and shares the same platform as our EAMP, electronic air measurement probes. 

more information & related documents

Family Description

Ruskin's EFAMS electronic fan-inlet air measurement station utilizes thermal dispersion technology combined with low-pressure drop aerodynamic sensors to measure the airflow at the highest velocity point in the system. This lower pressure drop equates to lower cost of operation over the life of the building when compared to other fan inlet devices. The unique design does not rely on measurement of 100% of the air entering the fan, only measurement of an air flow that we know will track the actual air flow through the fan. The benefit is a more accurate air flow measurement (taking into account system effects) without adding a significant energy penalty, typical of most aftermarket fan inlet air measurement devices.