Pressure

WPR2 Series



Product Bar End
Product Bar End

WPR2 Series

Wet/Wet Differential Pressure Transducer with Remote Probes WPR2 Series

Wet/Wet Differential Pressure Transducer with Remote Probes

 

The ACI A/WPR2 Series remote wet to wet differential pressure transmitter is designed to reduce installation time and provide mounting flexibility, often eliminating the need for additional plumbing. They accurately measure wet media pressures in a variety of applications. Commonly used for monitoring pumps, these devices are also ideal for measuring pressure across filters, heat exchangers and compressors. The A/WPR2's enclosure opens conveniently to allow it to be reconfigured between three additional ranges (see order grid) and output of 4 to 20 mA (default), 0 to 5 VDC, or 0 to 10 VDC. The A/WPR2 Series can measure both uni or bi-directional pressure ranges as low as 10 psi and as high as 300 psi, depending on the unit. The A/WPR2 also features a push button auto zero function for remote calibration.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
WPR2-100-10 DP TRANS WET W REMOTE PROBE 0-100PSI 10FT CABLESINFO853.45477.93
WPR2-100-10-LCD DP TRANS WET REMOTE PROBE 0-100PSI 10FT CABLES LCDINFO1,023.13572.95
WPR2-100-20 DP TRANS WET W REMOTE PROBE 0-100PSI 20FT CABLESINFO902.94505.65
WPR2-100-20-LCD DP TRANS WET REMOTE PROBE 0-100PSI 20FT CABLES LCDINFO1,093.83612.54
WPR2-300-10 DP TRANS WET W REMOTE PROBE 0-300PSI 10FT CABLESINFO842.34471.71
WPR2-300-10-LCD DP TRANS WET REMOTE PROBE 0-300PSI 10FT CABLES LCDINFO1,034.24579.17
WPR2-300-20 DP TRANS WET W REMOTE PROBE 0-300PSI 20FT CABLESINFO902.94505.65
WPR2-300-20-LCD DP TRANS WET REMOTE PROBE 0-300PSI 20FT CABLES LCDINFO1,093.83612.54

Accessories

No accessories found
Features
  • Remote probes save on plumbing time / expense
  • Push button auto zero function
  • Remote auto zero function
  • Selectable ranges
  • Selectable output modes
  • Selectable PSI or BAR reading (LCD version only)
  • Out-of-range diagnostic output
Specifications

Supply Voltage: 16 to 36 VDC for 2-wire 4-20 mA output 16 to 36 VDC, 24 VAC (±20%) fir 0-5 VDC; 0-10 VDC outputs

Accuracy :±1.0% FSO (includes linearity, hysteresis and repeatability), ±1.5% for 0-10 & 0-30 psi range

Signal Output (Volts, Current):2 wire Linear 4-20 mA @ 250Ω (default), 3 wire; 0-5 VDC @ 5KΩ ; 0-10 VDC @ 5KΩ Field Selectable

Sensor Type: Ceramic capacitive

Adjustments (Z/S): Auto Zero button

Normal Measurement Range (Field selectable within range) :10/25/50 & 100 psi (uni and bi-directional) for 100 psi sensors 30, 75, 150 & 300 psi (uni and bi-directional for 300 psi sensor

Display: Dual color LED Red/Green, Green=Normal

Overpressure (Burst): 1500 psig

Max Operating Pressure (Proof): 3X F.S (A/WPR2-100 Series), 2X F.S. (A/WPR2-300 Series)

Operating Temperature: Sensors: -30° to 120℉ (-22° to 248℃), Electronics/Housing/Cables: 32° to 167℉ (0° to 75℃)

Operating Humidity: 10 to 90% Non-condensing

Wetted Parts: 304 stainless steel

Media Compatibility: Gasses, refrigerants, ammonia and water-based fluids

Process Connection: 1/4″ -18 NPT Male (304 stainless steel)

Wiring Terminations: Screw connection terminal block

Enclosure Rating: NEMA 4X/IP66

Dimensions: 3.93″W x 3.0″H 5.10″L

Warranty: 5 years limited