Supply Voltage: Not required
Contact Type: SPDT
Contact Rating: 300 VA pilot duty @ 115-277 VAC,
:5A non-inductive to 277 VAC
Setpoint (SP):(025, 031) Adjustable from 0.15 to 5.0″ WC w/ screw
Dial Pressure Gauge: (092) Adjustable from 0.15 to 2.0″ WC w/ screw
Differential :
Model:See model number
(025, 031) Progressive by SP from 0.05″ to 0.3″ WC:
(092) Progressive by SP from 0.05″to 0.2" WC:
Reset Automatic: reset by differential
Visual Indication: None
Sensor Type: Silicone Diaphragm
Operating Pressure Range: 0.15 to 5″ WC
Overpressure: (Burst) 13.8″WC (3.45kPa)
Max Operating Pressure: (Proof) 13.8″WC (3.45kPa)
Operating Temperature :-40° to 180℉(-40 to 82℃)
Operating Humidity: 10 to 90% Non-condensing
Wetted Parts: Silicone
Media Compatibility :Inert dry air
Process Connection: Tri-Barb (1/8",1/4″. 5/16″) tubing or 1/4″ comp.
Wiring Terminations :3 Terminals (SPDT)
Mounting :Vertical bracket, 4 slots 0.2″x 0.3.9″ (0.5 x 1cm)
Enclosure Rating :Zink-plated steel, NEMA 1
Dimensions: 4.63″ w x 4.1″ h x 2.7″ d, (11.7 x 10.4 x 6.7 cm)
Weight: 0.9 lb (0.4 kg)
Approvals: UL File #MH6213, CSA
Warranty: 2 year