Signal Output: 4-20 mA (2-wire), 0-5 or 0-10 VDC (3-wire), switch selectable
Accuracy: ±1.0% F.S.O
Burst Pressure: 60″ W.C. (200″ for 12″ and 20″ models)
Response Time: 250 ms
Operating Humidity: 10%-90% RH, non-condensing
Operating Temperature: 32° to 158℉ (0° to 70℃)
Wiring Terminations: Screw terminal block (14-22 AWG)
Supply Current: <4 mA
Thermal Effect: <±3.0% over compensated range
Measurement Type:Differential (two port), static, velocity, and total pressure
Power Supply:20-28 VAC/DC (non-isolated half-wave rectified)
Protection Circuitry:Reverse voltage protected and out limited
Output Drive Capabilities:Current: 400Ω max. @ 24 VDC; Voltage: 10kΩ min.
Pressure Connections:Barbed ports for 0.170″ ID flexible tubing
Optional Display:3-1/2 digit LCD, 0.4″ digit height
Compensated Temperature Range:32° to 122℉ (0° to 50℃)
Conduit Connection: Access hole for 1/2″ NPT conduit or cable gland
Enclosure: High impact black ABS, plenum rated with optional gasket; 3.3″H x 5.0″W x 2.1″D (8.4 x 12.7 x 5.3 cm)
Input Voltage Effect: Negligible over specified operating range
Media Compatibility: Non-corrosive, non-ionic fluids such as clean dry air or inert gases
Proof Pressure: 40″ W.C. (100″ for 12″ and 20″ models)
Stability: <±1.0% F.S.O per year
Zero Adjustments:Pushbutton auto-zero
Approvals: CE, RoHS
Weight: 0.4 lb (0.2 kg)
Warranty: 5 years