Supply Voltage:High voltage power: 100-240 VAC, 50-400 Hz or 132-240 VDC; Low voltage power: 24 VDC ±20%
Supply Current:
Accuracy: ±0.5% @ 77℉ (25℃) including hysteresis and repeatability
Stability: <± 1% per year
Signal Output:4-20 mA DC into 900Ω max.
Pressure Range:Ranges ≤ 2.5 in W.C.: 2 psi (13.8 kPa); 5″: 5 psi (34.5 kPa); 10″: 5 psi; 25″: 5 psi; 50″: 5 psi, 100″: 9 psi (62 kPa).
Thermal Effect:0.020%/℉ (0.036/℃) from 77℉ (25℃)
Response Time:250 ms
Operating Temperature:32° to 140℉ (0° to 60℃)
Process Connection:Compression fitting for use with 1/8″ ID x 1/4″ OD tubing (0.3 x 0.6 cm). Optional barbed fitting for 3/16″ ID tubing.
Media Compatibility:Air and non-combustible, compatible gases
Display:4 digit LCD 0.4″ height. LED indicators for set point and alarm status
Communication Ports:Modbus® RTU, RS485, 9600 baud
Enclosure Rating:Face designed to meet NEMA 4X (IP66)
Housing Material:ABS plastic, UL approved 94-V-0
Panel Cutout:1.8 x 3.6 in (4.6 x 9.1 cm)
Mounting Orientation:Mount unit in horizontal plane
Size:1/8 DIN
Weight:
Approvals:
Warranty:1 year