Supply Voltage: 11 to 32 VDC
Accuracy:±1% full scale
Signal Output: 4-20 mA @ 700Ω (Source)
Sensor Type Capacitive: 5″WC
Adjustments: (Z/S) Zero & Span trim POTs, Non-interactive, (Bi-dir is interactive)
Normal Measurement Range: 0 to 10″WC, Bi-Directional
Overpressure :(Burst) ±5 to 11″WC (1.25 to 2.88 kPa)
Max Operating Pressure :(Proof) ±0.3 to 10″ WC (74 Pa to 2.5 kPa)
Operating Temperature: 32 to 115℉ (0 to 45℃)
Operating Humidity: 10 to 90% Non-condensing
Wetted Parts: Silicone
Media Compatibility Inert: dry air
Process Connection: 3/16″ OD ABS Plastic, for 1/4″ OD tubing
Wiring :2, #6 Terminals
Mounting: 2 , #8 screws
Enclosure Rating: Polyphenylene oxide (NORYL™), NEMA 1
Dimensions: 5.15″ w x 3.0 h x 1.48 d, (13.08 x 7.62 x 3.76 cm)
Weight: 0.42 lb (0.19 kg)
Approvals :CE
Warranty: 1 year