Pressure

BVA-5



Product Bar End
Product Bar End

BVA-5

Bypass Valve Assembly BVA-5

Bypass Valve Assembly

 

Differential pressure transmitters are often installed in systems with pressures much higher than the differential pressure being monitored. During installation, start-up, or shutdown, the pressure differential may exceed the transmitter differential pressure rating, resulting in severe damage to the transmitter. The Kele Model BVA-5 Bypass Valve Assembly will minimize this possibility. When it is purchased with a transmitter, the transmitter is assembled in a NEMA 1 or NEMA 3R enclosure with two isolation valves, an equalizing valve, and two vent valves mounted and piped. Optional pressure snubbers are also available mounted on the Model BVA-5.The Model BVA-5 is designed for use on systems with maximum pressures less than 150 psig (1034.3 kPa) at 150 Deg. F (65 Deg. C).


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
207ACBH-2 BULKHEAD FITTINGIn Stock19.3810.85
215PNL-2-15 1-1/2IN CLOSE NIPPLEIn Stock8.004.48
215PNL-2-25 2-1/2IN CLOSE NIPPLEIn Stock11.506.44
215PNL-2-40 4IN CLOSE NIPPLEIn Stock14.288.00
2202P-2-2 ELBOWIn Stock7.504.20
BVA-5-231G 5 VALVE BYPASS FOR SETRA 231GIn Stock1,066.00596.96
BVA-5-DPW 5 VALVE BYPASS FOR KELE DPWIn Stock807.00451.92
BVA-5-DPW-3R 5 VALVE BYPASS FOR KELE DPW W/ NEMA 3R ENCLINFO862.17482.82
BVA-5-MAM 5 VALVE BYPASS FOR MAMAC PR282In Stock673.00376.88
BVA-5-PW2 5 VALVE BYPASS FOR VERIS PW2In Stock773.00432.88
BVA-5-R 5 VALVE BYPASS FOR 360CIn Stock680.00380.80
BVA-5-SET 5 VALVE BYPASS FOR SETRA M230 OR SETRA 2301In Stock673.00376.88
BVA-5-SET-3R 5 VALVE BYPASS SETRA M230 OR 2301 W/ NEMA 3R ENCLINFO681.00381.36
BVA-5-VER 5 VALVE BYPASS FOR VERIS PWIn Stock725.00406.00
BVA-5-VER-3R 5 VALVE BYPASS FOR VERIS PW W/ NEMA 3R ENCLINFO684.00383.04
BVA-5-W 5 VALVE BYPASS FOR AMPHENOL W30In Stock768.00430.08
BVA-5W-3R 5 VALVE BYPASS FOR AMPHENOL W30 W/ NEMA 3R ENLCINFO945.00529.20

Accessories

No accessories found
Specifications

Family Name: Enclosed pressure bypass and equalizing assembly

Main Use: Pressure Transducer Diaphragm Protection

Construction: Brass fittings, Nylon valves w/ plastic tubing

Operating Pressure: 150 PSIG (1035 KPa)

Overpressure (Burst): 150 PSIG (1035 KPa)

Operating Temperature :150℉ (66℃)

Operating Humidity :0 to 98% Non-condensing

Media Compatibility: Liquid/Gasses compatible w/Brass & copper fittings and Nylon tubing

Process Connection: Two- 1/8″ FNPT (High/Low)

Mounting : Four holes 0.28″ (0.7 cm) dia NEMA 1

Enclosure Rating : NEMA 1, (NEMA 3R opt.)

Dimensions :

W30, DPW :18″H x 12″W x 4″D (45.7 x 30.5 x 10.2 cm)

PR262, M230: 12″H x 10″W x 4″D (30.5 x 25.4 x 10.2 cm)

NEMA 3R :16″H x 12″W x 6″D (40.6 x 30.5 x 15.2 cm)

Weight: 15.5 lb (7.0 Kg)

Warranty :1 Year

Certifications


Download Additional Data

document   BVA-5 Catalog Page