Supply Voltage:24 VAC ±10% or 24 VDC ±10%
Supply Current:
: 120 mA maximum @ 24 VAC
:50 mA Maximum @ 24 VDC
Dip Switches:Sliding window size is DIP switch-selectable for 5-, 15-, or 30-minute periods; kWh pulses to produce full-scale output are DIP switch selectable from 10 pulses per period to 18,000 pulses per period
Input Signal:24 VAC/VDC switched through electronic or mechanical contact closure
:Input Current 15 mA non-inductive at 24V
:Max Pulse Rate 10 pulses/seconds
Output Signal:4-20 mA factory set, adjustable 0-20 mA zero and span; 2-10 VDC factory set, adjustable 0-18 VDC (both outputs can be used simultaneously)
Output Impedance:Maximum output resistance 650Ω for mA output; maximum current available from voltage and current outputs combined is 25 mA
LED Indication:
:Green status LED (L2)
:Steady green = normal
:Slow flashing green = calibration mode
:Rapid flashing green = kW demand overflow
:Red signal LED (L1) = contact closure on the utility meter kWh contacts (LED is off when contacts open)
:Note: L3 and L4 stay ON during operation
Mounting:3.25" (8.3 cm) snap track (supplied with unit)
Dimensions:3.25"H x 4.6"W x 1"D
(8.3 x 11.7 x 2.54 cm):
Weight:0.39 lb (0.17 kg)
Warranty:18 months