E50 Series Power Meter E50 Series

E50 Series Power Meter

 

The Veris E50 Series power meter provides a solution for measuring energy data with a single device. Inputs include Control Power, CT, and 3-phase voltage. The E50 supports multiple output options, including solid state relay contacts, BACnet, Modbus (with or without data logging), and pulse. The LCD screen on the faceplate allows instant output viewing. The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E50 can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The meter is not sensitive to CT orientation to reduce installation errors.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
AE010 NEMA 4 FIELD ENCLOSURE In Stock254.66203.73
AE011 KEY AND LOCK FOR AE010 ENCLOSURE INFO127.32101.86
AE012 NEMA 4X ENCLOSURE FOR E5X SERIES METERS In Stock244.82195.86
AH02 FUSE PACK, SINGLE INFO78.9063.12
AH03 FUSE PACK, DOUBLE INFO156.50125.20
AH04 FUSE PACK, TRIPLE In Stock235.01188.01
E50B1 PWR MTR, PULSE OUTPUT, 90-600V In Stock870.29696.23
E50C1 PWR MTR, MODBUS KW & KWH, 90-600V INFO877.18701.74
E50C2 PWR MTR, MODBUS & PULSE OUTPUT, 90-600V INFO975.91780.73
E50C3 MODBUS & PULSE OUTPUT, DATA LOGGING, 90-600V In Stock1,165.15932.12
E50F2 LON & PULSE OUTPUT, 0.5% ACCURACY, 90-600V INFO1,344.481,075.58
E50F5 LON & PULSE OUTPUT, DATA LOGGING, 90-600V INFO1,498.521,198.82
E50H2 BACNET MSTP & PULSE OUTPUT, DATA LOG 0.2% 90-600V In Stock1,171.41937.13
E50H5 BACNET MSTP & PULSE OUTPUT, DATA LOGGING, 90-600V In Stock1,364.301,091.44
E51C2 BI-DIRTNL0.2% ACC. MODBS&PLSE OUTPUT90-600V INFO1,175.05940.04
E51C3 BI-DIRTNL0.2% ACC.MODBUS&PULSE OUTPT, DATA LOG INFO1,324.681,059.74
E51C3A BI-DIRTNL0.2% ACC.MODBUS&PULSE OUTPT,CT INTGRTR INFO1,336.781,069.42
E51H2 BI-DIRECTIONAL BACNET & PULSE OUTPUT 0.2% 90-600V INFO1,375.291,100.23
E51H5 BI-DRTNL BACNET & PULSE OUTPUT 0.2% DATA LOG BTL INFO1,498.521,198.82

Accessories

No accessories found
Features
  • Monitors 1, 2, or 3 phase services
  • Monitors services up to 600 VAC directly and 32,000 VAC with use of a potential transformer
  • Accepts .333 VAC or 1V Current Transformer's (sold separately)
  • DIN mounting for easy installation
  • ANSI 12.20 0.5% accuracy
  • BACnet, Modbus RTU or pulse output
  • 90-600 VAC for application versatility
  • Bright backlit LCD with easy visibility
  • Pulse and phase loss alarms standard
  • User-enabled password protection
  • Approved for California Solar applications
Specifications

Supply Voltage:

 :UL 90 VAC (L-N) to 600 VAC (L-L), 50/60Hz

CE:90 VAC (L-N) to 300 VAC (L-L), 50/60Hz

Monitored Voltage: Line to Line: 90 to 600 VAC

Line to Line with potential transformer: 601 to 32000 VAC :

Monitored Current:5 to 32,000 Amps

Availble CT's :0 to 0.333 V or 0 to 1 V

Input Signal:2 (E50H5 only) Pulse Solid-State or mechanical contacts (current less than 1 mA) Minimum Pulse Width 20 msec

Outputs:

 :E50B1 Reactive energy pulse 30 VAC/DC

 :E50C1 RS-485 2-wire Modbus RTU Basic Data Set

 :E50C2/E51C2 RS-485 2-wire, Modbus RTU Full Data Set

 :E50C3/E51C3 RS-485 2-wire Modbus RTU Full Data Set, data logging

 :E50H3 RS-485 2-wire BACnet MS/TP Full Data Set, data logging

Accuracy:Real power and energy 0.2% (ANSI C12.20, IEC 62053-22 Class 0.2S)

Operating Temperature:

Meter:22° to 158℉ (-30° to 70℃)

Display:14° to 122℉ (-10° to 50℃)

Operating Humidity:< 95% RH non-condensing

Enclosure Rating:NEMA 1

Mounting:DIN Rail or 3-point screw mount

Dimensions:2.3" x 4.2" x 3.6" (5.9 cm x 10.7 cm 9.1 cm)

Weight:0.62 lb (0.28 Kg)

Approvals:CE, UL508, UL File #E339785, RoHs

Warranty:5 years