Power Monitoring and Protection

CX, SCX Series (Voltage)



Product Bar End
Product Bar End

CX, SCX Series (Voltage)

AC Current Transducers with Voltage Output CX, SCX Series (Voltage)

AC Current Transducers with Voltage Output

 

The Kele CX/SCX Series AC current transducer with voltage output can be used to directly monitor up to 200A and output a 0-5 or 0-10 volt DC signal. Well suited to building automation systems, BAS, the transducer is available in a split-core design that allows for easy installation on the existing wiring or in a lower cost solid-core version.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
CX05V150 CURR XDUCR, 0-50/100/150A, SOLID CORE, 0-5VDC OUT INFO63.6750.94
CX05V200 CURR XDUCR, 0-200A, SOLID CORE, 0-5VDC OUT In Stock63.6750.94
CX05V50 CURR XDUCR, 0-10/20/50A, SOLID CORE, 0-5VDC OUT In Stock63.6750.94
CX10V100 CURR XDUCR, 0-100A, SOLID CORE, 0-10VDC OUT INFO70.1456.11
CX10V200 CURR XDUCR, 0-200A, SOLID CORE, 0-10VDC OUT In Stock70.1456.11
CX10V50 CURR XDUCR, 0-10/20/50A, SOLID CORE, 0-10VDC OUT In Stock70.1456.11
SCX05V150 CURR XDUCR, 0-50/100/150A, SPLIT CORE, 0-5VDC OUT In Stock93.7074.96
SCX05V200 CURR XDUCR, 0-200A, SPLIT CORE, 0-5VDC OUT In Stock93.7074.96
SCX05V50 CURR XDUCR, 0-10/20/50A, SPLIT CORE, 0-5VDC OUT In Stock93.7074.96
SCX10V150 CURR XDUCR, 0-50/100/150A, SPLIT CORE,0-10VDC OUT In Stock93.7074.96
SCX10V200 CURR XDUCR, 0-200A, SPLIT CORE, 0-10VDC OUT In Stock93.7074.96
SCX10V60 CURR XDUCR, 0-10/20/60A, SPLIT CORE, 0-10VDC OUT In Stock93.7074.96

Accessories

No accessories found
Features
  • May eliminate the need for current transformers
  • Small size
  • No power supply needed
  • Split-core model easily installed over existing cable
  • UL listed, CE certified
Specifications

Frequency:

CX:40-100 HZ

SCX:50-100 Hz

Measurement Range:Up to 200 Amps

Output:0-5 VDC or 0-10 VDC @ 1 MΩ typical

Insulation Class:600 VAC, insulated conductors

Response Time:200 ms typical, 0-90%

Accuracy:

CX:± 2% FSO (5-100% of range)

SCX:± 2% FSO (10-100% of range)

Operating Temperature:5° to 140°F (-15° to 60°C)

Operating Humidity:5-90% RH, non-condensing

Enclosure Rating:NEMA 1, ABS/PC, UL94 V-0

Window Size:0.8″ (2.03 cm)

Termination:14 to 22 AWG

Dimensions:

CX:2.65″H x 2.6″W x 0.98″D (6.7 x 6.6 x 2.5 cm)

SCX:3.05″H x 3.0″W x 0.98″D (7.8 x 7.6 x 2.5 cm)

Weight:0.25 lb (0.11 kg)

Approvals: UL File #E339785, CE

Warranty:5 years

Certifications