Connections:Barbs for 5/32" OD poly tubing
Number of Pipes:1 or 2 depending on model selected
Sensor Element:Bimetal
Sensitivity:
:T4002 Adjustable from 0.75 to 4 psig/℉ (9 to 50 kPa/℃)
:T4054/T4100 Adjustable from 1 to 3 psig/℉ (12 to 38 kPa/℃)
Setpoint Range:55° to 85℉ (13° to 29℃)
Setpoints:
:T4002/T4100 Single
:T4054 Dual
Remote Bulb:No
Air Consumption:
:T4002 20 scim (5 mL/s)
:T4054 38 scim (10 mL/s)
:T4100 25 or 45 scim (7 or 12 mL/s), depending on restrictor
Operating Temperature:-20° to 130℉ (-29° to 54℃)
Mounting:Wall
Maximum Operating Pressure:25 psi (170 kPa)
Dimensions:2.1"H x 3.1"W x 1.8"D (5.3 x 8.0 x 4.5 cm)
Weight:0.4 lb (0.2 kg)
Warranty:1 year