Control Action: Direct acting
Connections: Barbs for 5/32″ OD poly tubing
Number of Pipes: 2 pipe
Sensor Element: Bellows
Sensitivity Adjustment: 2 1/4 psi/℉ (27.0 kPa/℃)
Setpoint Temperature Ranges:60 to 85℉ (10 to 30℃)
Temperature Response: 0.5℉ to (0.3℃)
Dial Graduations: 2℉ (1℃)
Factory Settings:
Calibration: 72℉ (22℃) 7.5 psi (52 kPa)
Sensitivity: 2.5 psi/℉ (31 kPa/℃)
Limit Stop Adjustment:45℉ and 85℉ (7℃ and 30℃)
Maximum Operating Pressure:30 psi (207 kPa)
Normal Air Pressure: 18 psi (124 kPa)
Nominal Air Consumption:10 scfm (2.7 ml/sec
Temperature:
Storage Temperature:-10 to 110℉ (-23 to 43℃)
Ambient Operating Temperature :40 to 110℉ (4 to 43℃)
Standard Cover: Brass
Dimensions: 5 5/8″H x 2 7/8″W x 2 3/16″D
: (143 x 73 x 56 mm)
Shipping Weight: 0.7 lbs. (0.3 kg)
Warranty: 1 year