Device Operation:
Supply Voltage :1 or 2, Lithium 3.0V 1400 mAh
Batteries:Duracell, DL123A, (Included)
Battery Life:4-5 years @75 second interval
Sensor Type :Temperature, 20K-2 thermistor internal
Probe length :Stainless Steel, 1/4″ dia x 2″ length
:CL2P Cable (Cable length per order)
Transmitted Range Value :
SST2630A :Overall Range, 40° to 200℉, (-40° to 93℃)
Transmitted Accuracy:
Temperature :±1.0℉ (±0.55℃)
Indication:LED on Transmit and data link conformation
A/D resolution:12 bit (4095 counts)
Mounting :Direct to wall w/tabs
Wiring:None
Operating Temperature:14° to 140℉ (10° to 60℃)
Operating Humidity :5 to 65% RH (non-condensing)
Construction :Polycarbonate (NEMA 4), ABS (NEMA 1)
Enclosure Rating :NEMA 4 (UL 94 5VA), NEMA 1 (UL 94 HB)
Dimensions :1.75″H x 3.00″W x 5.75″D, Probe ∅ 0.25″, (4.44 x 7.92 x 14.6 cm)
Weight :1.2 lb (0.54 kg)
Warranty :1 year
NEXT COLUMN:
Radio Transmitter:
Protocol:Proprietary (ACI), IEEE 802.15.4-2003/2006
:Data-Link LED confirms receiver reception
Frequency:902-928 MHz
Channel Network :1
Modulation:Direct Sequence Spread Spectrum (DSSS)
Transmit Power:11.2 mW (11 dBm)
Receiver Sensitivity:-110db
Open Air Range:5,280 ft (1,600m) Open air
:200’- 500’ (61-152 m) in building
Low Battery Indication:Yes, LED
Transmission time :20ms
Transmission Interval :75 seconds standard, (Can be factory programmed at 300 sec)
Antenna:Internal
Channels:One
Device Addresses :100 transmissions per minute
Programming:Program cable & laptop (free SW)
Repeater Capable :Yes, (can increase open air range x2)
Compliance:FCC ID# T4F061213RSO, RoHS