Device Operation:
Supply Voltage :3.6 VDC, Battery power only
Batteries: Two AA 3.6V batteries (Included)
Battery Life :8 years @20 second intervals
Sensor Type :Temperature, 10K-2 thermistor
Transmitted Range Value : -40° to 185℉ (-40° to 85℃)
Accuracy:Thermistor, 10K type 2, ±0.5℉ (±0.32℃)
Indication :LED on Transmit
A/D resolution :10 bit (1024 counts)
Mounting :Strap-on to pipe w/ties then insulate
Wiring :None
Operating Temperature: -40° to 185℉ (-40° to 85℃)
Operating Humidity:0% to 100% RH, non-condensing
Construction :UV-Resistant Polycarbonate, UL94 V-0
Enclosure Rating :IP-66
Dimensions:4.1″H x 5.0″W x 2.5″D, (10.4 x 12.7 x 6.4 cm)
Weight :1.0 lb (0.45 kg)
Warranty :2 year
Radio Transmitter:
Protocol:Proprietary (Point Six)
Frequency:418 MHz
Modulation:Frequency Modulation
Transmit Power:1mW ( 0 ㏈m)
Receiver Sensitivity:N/A
Open Air Range:100 ft (30m)
Low Battery Indication:None
Transmission time:20ms
Transmission Interval:20 seconds standard, (Can be factory programmed 10-300 s)
Antenna:Internal
Channels:One
Device Addresses:100 transmitters within 100'
Programming:Push button in field
Repeater Capable:Yes, (can increase open air range x10)
Compliance:RoHS
:Temp. Only FCC ID# T4F060811TEMP