Device Operation:
Supply Voltage 3.6 VDC, Battery power only:
Batteries Two AA 3.6V lithium batteries (Included):
Battery Life ˜ 8 years @20 second intervals:
Sensor Type Temperature, 10K-2 thermistor:
Transmitted Range Value -40° to 185℉ (-40° to 85℃):
Accuracy Thermistor, 10K type 2, ±0.5℉ (±0.32℃):
Indication LED on Transmit:
A/D resolution 10 bit (1024 counts):
Mounting 1/2″ NPT Direct to well:
2″ probe 1.5″L from tip to 1/2″ NPT thread, 1/4″ diameter:
4″ probe 3.5″L from tip to 1/2″ NPT thread, 1/4″ diameter:
8″ probe 7.5″L from tip to 1/2″ NPT thread, 1/4″ diameter:
Wiring None:
Operating Temperature -40° to 185℉ (-40° to 85℃):
Operating Humidity 0% to 100% RH, non-condensing:
Construction UV-Resistant Polycarbonate, UL94 V-0:
Enclosure Rating IP-66 :
Dimensions 4.1″H x 5.0″W x 2.5″D (10.4 x 12.7 x 6.4 cm):
Weight 1.0 lb (0.45 kg):
Warranty 2 year:
NEXT COLUMN NEXT COLUMN NEXT COLUMN NEXT COLUMN NEXT COLUMN:
Radio Transmitter:
Protocol (Proprietary, ZigBee, EnOcean) Proprietary (Point Six):
Frequency (MHz, GHz) 418 MHz:
Modulation (DSSS, FHSS) Frequency Modulation :
Transmit Power (db. and mw) 1mW ( 0 ㏈m):
Receiver Sensitivity (db. and mw) N/A:
Open Air Range (Ft, Meters) 100 ft (30m) :
Low Battery Indication, (Yes, No, How) None:
Transmission time (ms) ˜ 20ms:
Transmission Interval 20 seconds standard, (Can be factory programmed 10-300 s):
Antenna (internal, remote) Internal:
Channels (max #) One:
Device Addresses (max number) 100 transmissions per minute:
Programming (how) Push button in field:
Repeater Capable Yes, (can increase open air range x10):
Compliance (FCC, RoHS, IEEE) RoHS:
Temp. Only FCC ID# T4F060811TEMP: