Supply Voltage:24 VDC @ 20.8 mA
Accuracy: ±0.2% of span in air
Signal Output:4-20 mA @ 500Ω two-wire
Measurement Range:
LU23 :8" to 18.0' (20 cm to 5.5 m)
LU27 :4" to 9.8' (10 cm to 3.0 m)
LU28 :8" to 26.2' (20 cm to 8.0 m)
LU29: 8" to 32.8' (20cm to 10 m)
Memory: Non-volatile
Deadband:
LU23: 8″ (20 cm) from sensor
LU27:4" (10 cm) from sensor
LU28/29:8" (20 cm) from sensor
Operating Pressure:30 psig (206.9 kPa)
Process Temperature:-4° to 140℉ (-20° to 60℃)
Beam Width:
LU23: 3″ (7.6 cm)
LU27:2" (5.1 cm)
LU28/29:3" (7.6 cm)
Fail Safe:Selectable: 4 mA, 20 mA, 21 mA, 22 mA, or hold last signal
Resolution:
LU27:0.019" (0.5 mm)
LU28/29:0.079" (2.0 mm)
Process Connection:
LU23: 2″ NPT
LU27:1" NPT
LU28/29:2" NPT
Cable Length:10' (3m) length
Operating Temperature:-31° to 140°F (-35° to 60°C)
Enclosure Rating:NEMA 6P (UL 50 Type 6P) Polycarbonate
Dimensions: 2.9"H x 4.1"W x 4.1"D (7.4 x 10.5 x 10.5 cm)
Weight:
w/o bracket: 1.5 lb (0.7 Kg)
w/ bracket:2.1 lb (0.95 Kg)
Approvals: CE, FM, RoHS
Warranty: 1 year