Supply Voltage:24 VDC@ 600 mA max
Relay Type:1 Form C Summary Alarm Relay, 6 Form C alarms, one per input/zone
Relay Rating:1 A @ 24VDC, 0.5 A resistive @ 120 VAC configurable for supervised or non-supervised, latched or non-latched
Communication Ports:EIA-232: 9600 baud; Parity none; 8 data bits, 1 stop bit
EIA-485: 1200, 2400, 9600 or 19,200 baud; Parity none, odd, even (programmable); 8 data bits, 1 stop bit:
Protocol:Terminal Emulation, VT100 compatible
Modbus RTU :
Audible Alarm:85DBA @ 2ft (0.6m); re-sound (disabled, 8,16 or 24 hours)
Input:RLE Leak Detection Cable (not included)
spot detectors (SD-Z or SD-Z1 only; not included):
Cable Input Each input requires LC-Kit: 15ft (4.57m) leader cable and EOL (not included):
Maximum Length: Up to 1,000ft (305m) of conductive fluid sensing cable and/or spot detectors per zone; 6,000ft (1830m) total, or 700ft (213m) of chemical sensing cable per zone; 4,200ft (1280m) total:
LED Indication:Alarm: red; Cable Fault: yellow
Response Time:When used with conductive fluid sensing cable or chemical sensing cable, 20-3600sec, software adjustable in 10 second increments; ±2sec Dry Contact NO/NC
Altitude Limits:15,000ft (4572m) max.
Mounting:Wall mount enclosure
Operating Temperature:32° to 122°F (0° to 50°C)
Operating Humidity:5% to 95% RH, non-condensing
Dimensions:10.5"W x 8.0"H x 2.0"D (267 x 203 x 51 mm)
Weight:4 lb (1.82 Kg)
Approvals:CE, ETL, CSA, RoHS
Warranty:1 year