Supply Voltage:5 VDC (± 10%) @ 100 mA
Relay Type:Two Form C alarm relays (leak and fault)
Relay Rating:1 A @ 24 VDC, 0.5 A resisitive @ 120 VAC
LED Indication:Normal Operation: Green; Cable Fault: Flashing Orange; Leak Detected: Flashing Red
Response Time:<20 seconds, 10 sec typical
Sensitivity:3 jumper settings
Audible Alarm:85 db @ 4: w/enable, disable
Operating Temperature:32° to 122℉ (°0 to 50℃)
Operating Humidity:5 to 95% non-condensing
Altitude Limits:15,000 ft (4,572m) maximum
Mounting:Surface mount
Cable Length:300 ft (91m) maximum of conductive fluid sensing cable or 210 ft (64m) of chemical sensing cable (req. LC-KIT-M)
Dimensions:2.7″W x 4.4″H x 1.38″D
:(6.8 x 11.2 x 3.5 cm)
Approvals:CE, ETL, RoHS
Weight:0.2 lb (0.09 Kg)
Warranty:1 year