Accuracy:3% RH, 0-100%
Hysterosis:±0.1%
Thermal Effect:0.07% per °F
Supply Voltage:12-40 VDC, 12- 35 VAC (for Voltage model only)
Signal Output: 4-20 mA @ 725Ω, 0-5/10 VDC, thermistor, RTD
Measurement Range:
RH:0-100%
Temperature:-30° to 130℉ (-35° to 55°)
Operating Humidity:0-100% RH non-condensing
Operating Temperature:-30° to 130℉ (-35° to 55°)
Enclosure Rating:
Room:NEMA 1, plastic
Duct/OSA: NEMA 4
Wiring Terminations:Terminal block
Duct probe length:6″ (15.2 cm)
Weight:
Room:0.5 lb (0.25 Kg)
Duct:1 lb (0.45 Kg)
OSA:1 lb (0.45 Kg)
Approvals:RoHs, CE
Warranty:1 year