Accuracy:
Humidity:±2% (5 to 90% RH)
Temperature:±0.5℉ (0.27℃)
Supply Voltage:9.4-35 VDC (24V nominal)
Signal Output:4-20 mA @ 730Ω
Measurement Range:
Humidity: 0 to 100% RH
Temperature:
″EN″ Range:-20° to 140℉ (-29° to 60℃)
″S″ Range:0° to 100℉ (-18° to 38℃)
″H″ Range:40° to 90℉ (4° to 32℃)
Sensing Technology:
Humidity:Capacitive monolithic IC
Temperature:Platinum 1000Ω RTD 385 curve
Operating Temperature:
Room:-10° to 150℉ (-23° to 65℃)
Duct/OSA:-10° to 185℉ (-23° to 85℃)
Wiring Terminations:Nonpolar terminals (22-14 AWG wire)
Weight:
Room:0.19 lb (0.09 Kg)
Duct:1.20 lb (0.55 Kg)
OSA :1.20 lb (0.55 Kg)
Warranty: 3 years